Sensor Location -

Options AG39 and

AG41

Calculate the Setpoints with Two Furnace Sections

- Use the following formulas to calculate the controller

settings for Heat Stage 2 and Heat Stage 3 in a system

with two furnace sections.

T

SP

= Setpoints of Heat Stage Controllers (T

SP2

and T

SP3

)

T

SA

= Desired Supply Air Temperature

T

D

= Design (minimum) Entering Air Temperature

Formulas for two furnace sections:
Setpoint for Heat

Stage 2: T

SP2

= T

SA

- 0.46 (T

SA

- T

D

)

Setpoint for Heat

Stage 3: T

SP3

= T

SA

- 0.73 (T

SA

- T

D

)

Set Heat Stage

Controllers - applies

to Options AG41 and

AG42 only

For the convenience of the installer, the duct temperature sensor is factory installed

in the cabinet leg (See

FIGURE 49, page 47). Although the sensor has a mixing tube,

at this distance from the discharge it does not receive a true mix, so the temperature

read by the sensor will be slightly higher than the actual air entering the ductwork. The

system will provide comfort level heat if the selector is set slightly lower to compensate

for this reading. The offset temperature will vary with the application. If a direct correla-

tion of these two temperatures is required, move the duct sensor to a location in the

ductwork about 10-12 feet (3 - 3.7M) from the furnace discharge.
Systems with Option AG41 and AG42 have “heat stage controllers” that control opera-

tion of the "two-stage" furnace based on outside air temperature setpoints. Proper

setpoints are important to ensure the modulating furnace ("Heat Stage 1") is always in

control and avoids cycling

. The proper setpoint for each controller must be determined

from basic design information. Sizes 500, 600, and 800 with two furnace sections have

two heat stage controllers; Size 1200 with three furnace sections has four heat stage

controllers.
Follow the steps and example to determine appropriate setpoints. Follow the instruc-

tions to locate and set the controllers.

EXAMPLE : 3600 CFM, Power vented, 100%

Outside Air, -10°F Outdoor Winter Design, 75°F

Desired Supply Air

T

SP2

= 75

- [.46 x (75

- (-10))] = 75 - (.46 x 85) =

35.9
T

SP3

= 75

- [.73 x (75

- (-10))] = 75 - (.73 x 85) =

12.9
Set Stage Heat #2 Controller to 36°F
Set Stage Heat #3 Controller to 13°F

Calculate the Setpoints with Three Furnace Sections

- Use the following formulas to calculate the controller

settings for Heat Stage 2, Heat Stage 3, Heat Stage

4, and Heat Stage 5 in a system with three furnace

sections.

T

SP

= Setpoints of Heat Stage Controllers (T

SP2

, T

SP3

,

T

SP4

, T

SP5

)

T

SA

= Desired Supply Air Temperature

T

D

= Design (minimum) Entering Air Temperature

Formulas for three furnace sections:
Setpoint for

Heat Stage 2: T

SP2

= T

SA

- 0.30 (T

SA

- T

D

)

Setpoint for

Heat Stage 3: T

SP3

= T

SA

- 0.49 (T

SA

- T

D

)

Setpoint for

Heat Stage 4: T

SP4

= T

SA

- 0.65 (T

SA

- T

D

)

Setpoint for

Heat Stage 5: T

SP5

= T

SA

- 0.82 (T

SA

- T

D

)

EXAMPLE : 8850 CFM, Power vented, 100% Outside

Air, -10°F Outdoor Winter Design, 75°F Desired

Supply Air

T

SP2

= 75

- [.30 x (75

- (-10))] = 75 - (.30 x 85) = 49.5

T

SP3

= 75

- [.49 x (75

- (-10))] = 75 - (.49 x 85) = 33.3

T

SP4

= 75

- [.65 x (75

- (-10))] = 75 - (.65 x 85) = 19.8

T

SP5

= 75

- [.82 x (75

- (-10))] = 75 - (.82 x 85) = 5.3

Set Stage Heat #2 Controller to 49°F
Set Stage Heat #3 Controller to 33°F
Set Stage Heat #4 Controller to 20°F
Set Stage Heat #5 Controller to 5°F

Locate and Set the Heat

Stage Controllers

1. In the inlet air section, locate the heat stage controllers. The same type of

controller may also used as the optional high ambient limit control (Option BN2)

and as the mixed air controller that is part of certain air control options (Options

AR12, AR13, AR15, and AR16). Identify the controllers marked Heat #2 and Heat

#3 or Heat #2, Heat #3, Heat #4, and Heat #5.

2 Furnaces - Identify controllers marked Heat #2 and Heat #3; set as

calculated above.
3 Furnaces - Identify controllers marked Heat #2, Heat #3, Heat #4, and

Heat #5; set as calculated above.

2. Adjust each controller to the setpoint as determined in the calculation.