beautypg.com

Reznor RPBL Unit Installation Manual User Manual

Page 25

background image

Form I-SSCBL/RPBL, P/N 149159 R7, Page 25

Flashing

(field-supplied)

Concentric

Adapter Box

Wall or

Adjoining

Building

6 ft (1.8M) minimum

9-3/8” (238mm)

11” (279mm)

*18”

(457mm)

minimum

4 ft (1.2M)

maximum

Roof

*Inlet air cap must be at least 6”

higher than anticipated snow depth.

2” (51mm) if roof is combustible

Attach box to roof with brackets.

12” (305mm) minimum
Cold Climate NOTE:
In

geographic areas where

the design ambient is

-10°F or lower, this

minimum height is 24”

(610mm).

(Top of Box)

Combustion

Air Pipe

Concentric

Adapter

Box

Roof

Double-wall Vent

(flue exhaust) Pipe

Combustion

Air Inlet

Vent (flue

exhaust) Terminal

Seal with silicone

sealant supplied

with the kit.

Flashing

(field-supplied)

Shaded area represents

required continuous (no

joints) section of double-

wall vent pipe. Section of

pipe may extend higher.

One-piece of Double-

Wall Vent Pipe

Use taper-type reducer

to attach to vent run

a maximum of 6”

(152mm) from the box.

FIGURE 24 - Installation of Unit with Vertical Vent Terminal/Combustion Air Inlet (Option CC2)

Rear

View

Side View

Flue

Products

Outlet

Combustion

Air Inlet

FIGURE 25 - Flue Outlet

and Combustion Air

Inlet - Model RPBL

Optional Vertical Flue Discharge (Option CC3) for Model RPBL

These power vented furnaces are certified with four feet (1.2M) of vertical pipe attached

as shown in

FIGURES 26A and 26B. The distance is measured from the top of the unit

to the bottom of the vent cap. The option package includes the 5" vent cap, the adapter

assembly and the seal plate. (One package is required for each furnace section.) The

vent pipe and supports are field supplied. The straight pipe connecting the furnace to

the 90° elbow must be at least 18" (457mm) in length.

6.2.2 Venting Outdoor

Power Vented Model

RPBL

The screened flue gas and combustion air openings are located on the side of each

furnace section just above the control access panel (

FIGURE 25).

The positions of the openings discour-

age recirculation of combustion products

and provide for furnace operation in all

normal weather conditions.
Install a power-vented furnace so that

the flue discharge is

not directed at fresh

air inlets.

This manual is related to the following products: