9 RS485 Communication
9.11.3 Error flags
Bit
Meaning
7
6
5
Read parameter failed
4
Incorrect access key
9.12 Read status word
9.12.1 Request
RS485 Char
Use
Value / Comment
1
Start byte
COM_CRX_STATUS_RD
2
Address byte
Bus address
3
Checksum
9.12.2 Answer
RS485 Char
Use
Value / Comment
1
Start byte
COM_CTX_STATUS_RD
2
Address byte
Bus address
3
Motor status byte
4
Status byte
5
Checksum
9.13 Load “Parameter default values”
The command enables the “Parameter default values” to be loaded into the RAM. To save the “Default values” permanently the “Save
parameters” command must be executed (
see Chapter 9.9 Save parameters, page 85
).
9.13.1 Request
RS485 Char
Use
Value / Comment
1
Start byte
COM_CRX_PARAMETER_RESTORE
2
Address byte
Bus address
3…6
Access key
Customer password
7
Checksum