6 Parameterisation
82 parameters are available for parameterising the VDC-3-49.15-K4 and ECI-63.XX-K4 drive systems (
). These are managed
via the electronic class K4 and are set using the ebm-papst “Kickstart” PC software.
A detailed parameter description
see Chapter “10 Parameter Description”, page 94
.
6.1 Memory management
The K4 has a management function for the “RAM”, “custom” and “default” memory areas.
To edit the values you will need the password “custom access key”. This is set to 0 on delivery. If you change it, please ensure that it is not
lost.
6.1.1 “RAM” memory area
The motor operates with the values in the RAM area.
The memory class “appl func” can be changed (written) if the motor is at a standstill (IN A and IN B input to LOW). If the inputs are not set to
zero you will receive an error message in the status display.
The memory class “appl value” can be changed (written) while the motor is in operation and therefore directly affects the motor's perfor-
mance.
All values can be read out during operation or while the motor is at a standstill.
Parameters that are written in the “RAM” memory area with the “write” command are no longer available if the power supply fails or is
switched off.
6.1.2 “custom” memory area
To ensure that the data is available permanently, it must be located in the “custom” memory area. The data from the “RAM” area is not
written in the “custom” area unless the “store” command is used; after it has been moved the data is then permanently available. On
switching on the voltage, the data from the “custom” area is transferred into the “RAM” area.