Table 7-2. Troubleshooting – Electronic Control System (ECS/SP)

No.

Fault Indication

Probable Cause

Corrective Action

T1

System not operating.
All displays are blank.











1. External 120 VAC

power disconnected.

2. Defective fuse on

side of Control Box.

3. Defective ON/OFF

switch on Control
Box.






1. Ensure external circuit breaker is ON.

Check for 120 or 240 VAC power across
TB-2 terminal leads 101 (Line) and 102
(Neutral).

2. Check the fuse on the right side of the

Control box. Replace if blown.

3. Set ON/OFF POWER switch to the ON

(Up) position and verify that the switch
indicator lights. Also:

a. Verify that 120 VAC is present across TB-
2 terminal leads 101 (Line) and 102
(Neutral).
b. If voltage not present, replace ON/OFF
POWER switch.

T2

Temperature Controller is
ON, but Temperature
Indicators are blank

1. Circuit breaker

tripped

2. Defective 24 VAC

transformer in
Control Box

1. Reset the circuit breaker on the 24 VAC

step-down transformer.

2. Check the 120 VAC or 240 VAC power on

TB-2 (see Appendix B). Verify that 24
VAC is present across the Blue and
Brown wires terminated on TB-1. If 24
VAC is not present, replace the 24 VAC
transformer in the Control Box.

T3

Water Heater outlet temp.
consistently above
Setpoint by 10°F or more.
However, temperature is
below Over-Temp. limit
setting.

1. Temp. Controller is

not properly set.

2. Faulty Temp. Sensor

(thermocouple) is
connected to Temp.
Controller.

1. Refer to Chapter 4 – ADJUSTMENTS and

check current setting of Temp. Controller.
Readjust if necessary.

2. Verify Outlet Temp Sensor is securely

connected to cable plug. Replace the
Dual Sensor if necessary

T4

Over-Temp Alarm occurs
repeatedly.

NOTE

Audible alarms will be
generated if Outlet Temp
Sensor is open.
Erroneous temperature
readings will be displayed
if Sensor is shorted.

1. Over-Temp Switch

not properly set.

2. Open or shorted

Outlet Temp. Sensor
(thermocouple)
connected to Over-
Temp. Switch.

3. Over-Temp Switch is

defective.

1. Refer to Chapter 4 and check the current

setting of the ECS Over-Temp. Switch.
Readjust if necessary.

2. Check thermocouple connections

between Sensor connector plug and TB-1
terminal leads 111 (+) and 112 (-). If
connections are secure, replace Dual
Temp Sensor.

3. Replace Over-Temp Switch.

T5

Boiler Water Inlet audible
alarm activated

1. Boiler water temp. is

greater than 220°F.

2. Alarm setting is not

correct.

3. Indicator is defective.

1. Correct the boiler water temperature

supply to SmartPlate Heater.

2. Refer to para.4.3.2 to reset the alarm limit

to 220°F.

3. Refer to Chapter 8, para. 8.9 for

replacement instructions.