Rockwell Automation Flex/WebPak 3000 DC Drive ControlNet, Network Communication Board, 915FK2101 User Manual
Page 59
Register Map for FlexPak 3000 Drives
7-7
N10:166
ANLG
TACH
VOLTS
/1000
P.203
Config
1 = 0.1 volts/1000
RPM
N10:167
PULSE
TACH
PPR
P.207
Config
1 = 1
PPR
N10:168
PULSE
TACH
QUADRATURE
P.208
Config
0 =
OFF
, 1 =
ON
N10:169
OCL
PROP
TRIM
SELECT
P.813
Config
0 =
DISABLED
, 1 =
ENABLED
N10:170
OCL
FEEDBACK
SELECT
P.804
Config
0 =
NONE
1 =
CML
FEEDBACK
2 =
ANALOG
IN
1
3 =
ANALOG
IN
2
4 =
SPEED
LOOP
OUTPUT
5 =
ANALOG
AUTO
REFERENCE
6 =
NETW
IN
REG
1
7 =
NETW
IN
REG
2
8 =
NETW
IN
REG
3
N10:171
OCL
TYP
3
POSN
REG
P.814
Config
0 =
DISABLED
, 1 =
ENABLED
N10:172
MOTOR
HOT
FLD
AMPS
P.510
Config
1 = 0.01 amp
N10:173
FIELD
REF
SELECT
P.521
Config
0 =
REGISTER
1 =
ANALOG
MAN
TRIM
REF
2 =
ANALOG
IN
1
3 =
ANALOG
IN
2
N10:174
FIELD
DELTA
HIGH
LIM
P.587
Config
1 = 1 deg
N10:175
FIELD
LOSS
THRESHOLD
P.512
Config
1 = 1% of
MOTOR
HOT
FLD
AMPS
(P.510)
N10:176
FIELD
AUTO
WEAKEN
P.517
Config
0 =
DISABLE
, 1 =
ENABLE
N10:177
CT
TURNS
RATIO
P.010
Config
N10:178
MOP
RESET
ENABLE
P.116
Config
0 =
OFF
, 1 =
ON
N10:179
JOG
OFF
DELAY
TIME
P.121
Config
1 = 0.1 s
N10:180
STOP
DECEL
SELECT
P.122
Config
0 =
DECELERATION
TIME
1 =
RAMP
STOP
DECEL
TIME
N10:181
NOMINAL
AC
LINE
FREQ
P.306
Config
1 = 1 Hz
N10:182
NOMINAL
AC
LINE
VOLTS
P.307
Config
1 = 1
VAC
N10:183
PHASE
LOSS
DETECT
EN
P.609
Config
0 =
DISABLE
, 1 =
ENABLE
N10:184
DIG
OUT
1
SELECT
P.409
Config
0 =
LEVEL
DETECT
1
OUTPUT
1 =
LEVEL
DETECT
2
OUTPUT
2 =
IN
CURRENT
LIMIT
3 =
DRIVE
READY
4 =
NETW
COMM
STATUS
5 =
NETW
IN
REG
1 (
BIT
0)
6 =
NETW
IN
REG
2 (
BIT
0)
7 =
NETW
IN
REG
3 (
BIT
0)
N10:185
DIG
OUT
1
CONTACT
TYP
P.410
Config
0 =
NORMAL
OPEN
1 =
NORMAL
CLOSED
Table 7.1 – File N10:x (Drive Read/Write Parameters) for FlexPak 3000 Drives (Continued)
File
Address
Parameter Name
Parameter
Number
Type
Scale