4.3

Using Unscheduled Transfers

Use the unscheduled transfer portion of the Network Update Time (NUT) to:

read and write drive parameters that are not time-critical

read drive display data

read and write drive reference and feedback data that is not time-critical

read the status of Typed Write messages. The drive sends and receives Typed
Read and Typed Write messages. Refer to the appropriate instruction manual to
configure your system to use Typed messages.

Table 4.7 – WebPak 3000 Scheduled Drive Feedback Data

Name

Description (Drive to PLC)

Word 0 Drive Status Word 1

Indicates drive status

Bit 00 Ready

0 = Not Ready, 1 = Ready

Bit 01 Running

0 = Stopped, 1 = Running

Bit 02 Fault Active

0 = No fault, 1 = Fault

Bit 03 Jogging Fwd

0 = Not jogging fwd, 1 = Jogging fwd

Bit 04 Jogging Rev

0 = Not jogging rev, 1 = Jogging rev

Bit 05 Underwind Active

0 = Overwind, 1 = Underwind

Bit 06 Stopping

0 = Not stopping, 1 = Stopping

Bit 07 Tension On Active

0 = Not active, 1 = Active

Bit 08 Stall Tension Active

0 = Not active, 1 = Active

Bit 09 Current Memory Active

0 = Not active, 1 = Active

Bit 10 Current Limit

0 = Not limited, 1 = Current limited

Bit 11 Alarm Active

0 = Not active, 1 = Active

Bit 12 Current/Speed Active

0 = Not active, 1 = Active

Bit 13 Processing Error

0 = No processing error, 1 = Parameter processing error

Bit 14 Level Detect 1 Output

0 = Off, 1 = On

Bit 15 Level Detect 2 Output

0 = Off, 1 = On

Word 1 Reserved

Reserved

Word 2 Speed Feedback

The speed of the motor as measured by the drive. Range is ±4095.
The units depend on the value of

FEEDBACK

SELECT

(P.200).

1 = 1/4095 of

GEAR

IN

SPEED

(P.011).

Word 3 Current Feedback

The current being supplied by the drive. Range ±4095. Units are amps.
1 = 1/4095 of product of

MAXIMUM

CURRENT

(P.007) and

MOTOR

RATED

ARM

AMPS

(P.008).

Word 4 Network Output 1

Displays value selected by

NETW

OUT

REG

1

SELECT

(P.902).

Word 5 Network Output 2

Displays value selected by

NETW

OUT

REG

2

SELECT

(P.903).

Word 6 Network Output 3

Displays value selected by

NETW

OUT

REG

3

SELECT

(P.904).

Word 7 Unused

Unused.