3 setting cni prog/run mode (p.915) – Rockwell Automation Flex/WebPak 3000 DC Drive ControlNet, Network Communication Board, 915FK2101 User Manual

Page 18

background image

3-2

ControNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

3.3

Setting CNI PROG/RUN MODE (P.915)

CNI

PROG

/

RUN

MODE

(P.915) selects how the drive will respond when communicating

with a PLC that is put into program mode while

CONTROL

SOURCE

SELECT

(P.000) is set

to

NETWORK

. When the PLC is put into program mode, alarm A00006 (

CNI

PROGRAM

MODE

), is generated to indicate the change in operation of the drive. An alarm is not

generated when the PLC is returned to run mode, since that is considered normal
operation.

When

CNI

PROG

/

RUN

MODE

=

STOP

(1), the drive will coast/DB stop when the PLC is put

into program mode. The drive can be started only when the PLC is in run mode.

When

CNI

PROG

/

RUN

MODE

=

USE

LAST

REF

(2), the drive will not stop (if running) or

start (if stopped) when the PLC is put into program mode. The drive will continue to
use the last network reference received as its speed reference. This will continue until
the PLC is returned to run mode and a new reference value is received.

When

CNI

PROG

/

RUN

MODE

=

USE

TRMBLK

CNTL

(3), the drive will not stop (if running) or

start (if stopped) when the PLC is put into program mode (or returned to run mode).
The drive's terminal block will become the source for all control (run, jog, stop, fault
reset, direction and OCL enable) and speed (auto) reference signals.

For FlexPak 3000 drives, the Speed Loop PI Reset and Underwind/Overwind bits
cannot be changed while operating in this mode. They will remain at the last values
received from the network. This will continue until the PLC is returned to run mode
when control/reference will come from the network again.

Range:

STOP

(1),

USE

LAST

REF

(2),

USE

TRMBLK

CNTL

(3)

Type: Non-volatile, Configuration

Default:

STOP

(1)

3.4

Setting NETW COMM LOSS SELECT (P.901)
(FlexPak 3000 Drives Only)

NETW

COMM

LOSS

SELECT

(P.901) is not used in WebPak 3000 drives. For WebPak 3000

drives, a fault is generated when network communication is lost if

CONTROL

SOURCE

SELECT

(P.000) is set to

NETWORK

. This causes the drive to coast/DB stop. The drive

cannot be restarted until the fault is cleared.

!

ATTENTION:

CNI

PROG

/

RUN

MODE

(P.915) allows you to configure the

drive to continue to run when the PLC is put into program mode. You
must provide some form of hardwired stop in case of communication
loss, since stopping the drive through the network might not be possible.
Failure to observe this precaution could result in bodily injury or damage
to, or destruction of, equipment.

!

ATTENTION:

NETW

COMM

LOSS

SELECT

(P.901) allows you to configure

the drive to continue to run if a loss of network communication occurs.
You must provide some form of hardwired stop in case of communication
loss, since stopping the drive through the network might not be possible.
Failure to observe this precaution could result in bodily injury or damage
to, or destruction of, equipment.