4.2

Configuring Drive Reference and Feedback Data as
Scheduled Transfers

This section describes how to:

configure scheduled traffic for the drive

control the drive using the drive reference data

use scheduled drive feedback data

4.2.1 Configuring Scheduled Data Transfers

Before the drive can communicate on the ControlNet network, you must configure its
scheduled traffic information by using some type of ControlNet configuration software.
By configuring scheduled traffic, you define how much data the drive can send, how
often the data is sent, and where the data is written to and read from (mapped) in the
programmable controller.

You must configure each drive on the ControlNet network. Table 4.2 lists the
configuration information you must enter if you are using RSNetWorx

and a

PLC-5

.

Table 4.2 – ControlNet Scheduled Traffic Configuration Fields

In this field:

Enter this information:

Node

Enter the drive’s node number that you defined in P.900.

Slot
Message

These fields are not used by the drive.

Module

Enter FlexPak 3000 or WebPak 3000.

API

This field is read-only.

RPI

Enter how often you want to exchange scheduled data between the
programmable controller and the drive.

Connection Type

Select “Exclusive Owner.”
FlexPak 3000 and WebPak 3000 drives do not support Multicast
operation.

Input Address

Enter the programmable controller’s integer file number that will store
data received from the drive (drive feedback data).

Input Size

Enter the number of words of drive feedback data that you want the
programmable controller to receive from the drive (1 to 8).
See section 4.2.3 for information about the type of data that is sent.

Output Address

Enter the programmable controller’s integer file number that will store
data sent to the drive (drive reference data).

Output Size

Enter the number of words of drive reference data that you want the
programmable controller to send to the drive (1 to 8).
See section 4.2.2 for information about the type of data that is sent.

Status Address

Enter the programmable’s integer file number that will store the status of
the ControlNet connection to the drive.

Config Address
Config Size

These fields are not used by the drive.