Page 45

background image

Configuring SLC500 Applications

6-1

C

HAPTER

6

Configuring SLC500 Applications

Chapter 6 describes how to configure a SLC500 PLC on a ControlNet network with a
FlexPak3000 or Webpak3000 drive.

Both the 1747-SCNR and 1747-KFC15 modules are required to communicate fully
with a drive and both must be configured as drops on the ControlNet network. If the
application only calls for access to Drive Reference and Feedback Data (such as Drive
Control and Status Words), and does not call for access to any N10, N11, or N12 drive
parameters, the 1747-KFC card will not be required. However, Unscheduled
Messaging will not be possible and another connection option to the processor will be
required for downloading the required ladder logic.

The examples in this chapter reference a FlexPak3000 drive. A similar process can be
followed if your application uses a Webpak3000 drive with the appropriate ControlNet
Options Board. Your rack configuration for the Webpak3000 may be different then the
included examples. Adjust the examples to match your Nodes and Slots accordingly.

This chapter is intended for use by personnel familiar with the installation and
operation of the Reliance Drive and the installation, programming, I/O configuration
and operation of the SLC processor using RSLinx, RSLogix 5000 and RSNetWorx for
ControlNet software. Personnel should also be familiar with the system configuration
documentation.

6.1

Required Software and Equipment

Software and equipment required for configuring a SLC500 on a ControlNet network
is listed in table 6.1.

Table 6.1 – Required Software and Equipment

Equipment Description

Version

RSLinx Software

Version 2.20 or later

RSNetWorx for ControlNet software

Version 2.25 or later

RSLogix 500 software

Version 3.01 or later

SLC 500 Chassis w/appropriately sized Power Supply

SLC 5/03 processor (1747-L532)

or SLC 5/04 processor

OS 301 or higher

Any OS

ControlNet Scanner Module: 1747-SCNR

ControlNet RS-232 Interface: 1747-KFC15

PC with 1784-KXTC15 or 1784-PCIC interface card

Flexpak3000/Webpak3000 ControlNet Communications

Board (915FK2101)

Version 2.20 or later