6-2

ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives

6.2

Network Configuration

Configure the ControlNet network using RSLinx and RSNetWorx for ControlNet
software.

Using the parameters suggested in chapter 4 of this manual, configure scheduled
traffic with RSNetWorx, by doing a scanlist configuration of the 1747-SCNR module to
the drive. It is recommended that Input and Output files are used instead of M1 and
M0 files, as discrete I/O is more appropriate for critical data transfer. Make sure
keyswitch is in “program” position before download of configuration.

Input address should be [ I:x:y ] with x = slot of SCNR module and y = 1 or greater.
Output address should be [ O:x:y ] with x = slot of SCNR module and y = 1 or greater.

Input and Output size for Flexpak3000 and Webpak3000 drives = 8.

Important: Any address offset is limited by 31 words maximum minus the drive I/O

word size.

Figure 6.1 – Network Configuration: Connection Properties