8 netw comm status (p.908), 9 netw type & version (p.909) – Rockwell Automation Flex/WebPak 3000 DC Drive ControlNet, Network Communication Board, 915FK2101 User Manual
Page 20
3-4
ControNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives
3.6
Setting NETW OUT REG 2 SELECT (P.903)
NETW
OUT
REG
2
SELECT
(P.903) defines a parameter number whose value will be
monitored and saved in the network option board’s dual-port memory. For example,
setting this parameter equal to 588 will cause the value of
FIELD
DELTA
(P.588) to be
written to file address N10:48 in the dual-port memory for FlexPak 3000 drives,
address N10:88 for WebPak 3000 drives.
Range: -32768 to 32767
Type: Non-volatile, Tunable
Default: 0
3.7
Setting NETW OUT REG 3 SELECT (P.904)
NETW
OUT
REG
3
SELECT
(P.904) defines a parameter number whose value will be
monitored and saved in the network option board’s dual-port memory. For example,
setting this parameter equal to 588 will cause the value of
FIELD
DELTA
(P.588) to be
written to file address N10:49 in the dual-port memory for FlexPak 3000 drives,
address N10:89 for WebPak 3000 drives.
Range: -32768 to 32767
Type: Non-volatile, Tunable
Default: 0
3.8
NETW COMM STATUS (P.908)
NETW
COMM
STATUS
(P.908) indicates the status of network communication.
When
NETW
COMM
STATUS
=
NOT
ACTIVE
, the network option board is not
communicating on the ControlNet network.
When
NETW
COMM
STATUS
=
ACTIVE
, the network option board is communicating
properly with the ControlNet network.
Range:
NOT
ACTIVE
(1),
ACTIVE
(2)
Type: Read-only (output)
3.9
NETW TYPE & VERSION (P.909)
NETW
TYPE
&
VERSION
indicates the type of network board installed and its software
version. The format is of the form TV.VV, where:
T = board type:
2 = AutoMax, Profibus, InterBus
4 = DeviceNet (FlexPak 3000 drives only)
5 = ControlNet
V.VV = major and minor version numbers (e.g. 1.03)
Range: 10.00 to 99.99
Type: Read-only (output)