Standalone device – Rockwell Automation 284D On-Machine ArmorStart Accelerator Toolkit User Manual
Page 83
![background image](/manuals/581661/83/background.png)
Publication IASIMP-QS015C-EN-P - August 2011
83
ArmorStart Local Control Configuration
Chapter 4
5. Click Apply, then OK.
If the master scanner is currently scanning the ArmorStart device to which you are downloading, you
must first access the DeviceNet’s scanner’s scanlist to remove the device from the scanlist. If this new
logic results in different connection sizes, adjust the master scanner as follows:
a. Put the master in Idle mode.
This may mean turning a processor’s key switch to PROG.
b. Access the ArmorStart parameter’s to change the size of the connections (parameters 11 and 12,
Consumed and Produced IO Assy).
c. Download the device to the scanlist.
d. Click the Edit I/O Parameters button and verify the Rx and Tx size corresponds to the new
connection size.
e. Put the master in RUN mode for normal operation.
See
for examples of moving the ArmorStart device to the scanlist.
Standalone Device
Set the comms parameters if the ArmorStart is a
standalone device.
1. Select the parameters tab.
2. Set parameter 8 and 9 to Enabled.