Electromagnetic compatibility – Rockwell Automation 284D On-Machine ArmorStart Accelerator Toolkit User Manual
Page 56
![background image](/manuals/581661/56/background.png)
56
Publication IASIMP-QS015C-EN-P - August 2011
Chapter 2
System Layout and Wiring
Electromagnetic Compatibility
The following guidelines are provided for EMC installation compliance.
General Notes for Bulletin 284 Devices
• The motor cable should be kept as short as possible to avoid electromagnetic emission as well as
capacitive currents
• Conformity of the device with CE EMC requirements does not guarantee an entire machine
installation complies with CE EMC requirements. Many factors can influence total machine and
installation compliance.
• Using an EMI filter with any ArmorStart device rating, may result in relatively high-ground leakage
currents. Therefore, the filter must only be used in installations and solidly grounded (bonded) to the
building power distribution ground. Grounding must not rely on flexible cables and should not include
any form of plug or socket that would permit inadvertent disconnection. Some local codes may require
redundant ground connections. The integrity of all connections should be periodically checked.
Ground the ArmorStart Controller
Connect a grounding conductor to the terminal provided as standard on each ArmorStart Distributed Motor
Controller.