Armorstart device wiring – Rockwell Automation 284D On-Machine ArmorStart Accelerator Toolkit User Manual
Page 47

Publication IASIMP-QS015C-EN-P - August 2011
47
System Layout and Wiring
Chapter 2
ArmorStart Device Wiring
Wiring in an industrial control application can be divided into three groups; power, control, and signal.
Follow these recommendations for physical separation between these to reduce the coupling effect:
• Minimum spacing between different wire groups in the same tray should be 16 cm (6 in.).
• Run wire outside an enclosure conduit or have shielding or armor with equivalent attenuation.
• Run different wire groups in separate conduits.
• Minimum spacing between conduits containing different groups should be 8 cm (3 in.).
The table provides power, control, ground wire capacity, and tightening torque requirements. The power,
control, ground, and safety monitor terminals accept a maximum of two-wire per terminal.
Power, Control, Safety Monitor Inputs, Ground Wire Size, and Torque Specifications
Terminal Type
Wire Size
Torque
Wire Strip Length
Power and Ground
Primary/secondary terminal
1.5...4.0 mm
2
(16...10 AWG)
Primary terminal - 1.2 N•m (10.8 lb•in.)
Secondary terminal - 0.5 N•m (4.5 lb•in.)
9 mm (0.35 in)
Control and Safety Monitor Inputs
1.0...4.0 mm
2
(18...10 AWG)
0.7 N•m (6.2 lb•in.)
9 mm (0.35 in.)