Rockwell Automation 1761-HHP-B30 MicroLogix 1000 with Hand-Held Programmer (HHP) User Manual
Page 426
Appendix C
Valid Addresssing Modes and File Types
for Instruction Parameters
C–10
Instruction
Description
Instruction
Parameter
Valid Addressing
Mode(s)
Valid File Types
Valid Value
Ranges
STS
Selectable Timed Start
file
immediate, direct,
indexed direct
O, I, S, B, T, C, R, N
always equal 5
time
immediate, direct,
indexed direct
O, I, S, B, T, C, R, N
0–255
SUB
Subtract
source A
immediate, direct,
indexed direct
O, I, S, B, T, C, R, N
–32,768–32,76
f-min–f-max
source B
immediate, direct,
indexed direct
O, I, S, B, T, C, R, N
–32,768–32,767
f-min–f-max
destination
direct, indexed direct
O, I, S, B, T, C, R, N
Not Applicable
SUS
Suspend
suspend ID
immediate,
–32,768–32,767
TND
Temporary End
Not Applicable
TOD
Convert to BCD
source
direct, indexed direct
O, I, S, B, T, C, R, N
destination
direct
O, I. S. B. T, C, R, N
Not Applicable
TOF
Timer Off-Delay
timer
direct
T (element level)
Not Applicable
time base
immediate
0.01 or 1.00
preset
(contained in the
timer register)
0–32,767
accum
(contained in the
timer register)
0–32,767
TON
Timer On-Delay
timer
direct
T (element level)
Not Applicable
time base
immediate
0.01 or 1.00
preset
(contained in the
timer register)
0–32,767
accum
(contained in the
timer register)
0–32,767
XOR
Exclusive OR
address A
immediate, direct,
indexed direct
O, I, S, B, T, C, R, N
–32,768–32,767
address B
immediate, direct,
indexed direct
O, I, S, B, T, C, R, N
–32,768–32,767
destination
direct, indexed direct
O, I, S, B, T, C, R, N
Not Applicable