Appendix B
Programming Reference
B–8
Address
Bit
Classification
Description
S5/2
Control Register
Error
Dynamic
Configuration
If this bit is ever set upon execution of the END or TND
instruction, major error (0020) is declared. To avoid this type
of major error from occurring, examine the state of this bit
following a control register instruction, take appropriate
action, and then clear bit S:5/2 using an OTU instruction with
S:5/2.
S5/3
Major Error
Detected While
Executing
user-fault routine
Dynamic
Configuration
When set, the major error code (S:6) represents the major
error that occurred while processing the fault routine due to
another major error.
S5/4 to S5/7
Reserved
NA
NA
S5/8
Retentive Data
Lost
Status
This bit is set whenever retentive data is lost. This bit
remains set until you clear it. While set, this bit causes the
controller to fault prior to the first true scan of the program.
S5/9
Reserved
NA
NA
S5/10
STI Lost
Status
This bit is set whenever the STI timer expires while the STI
routine is either executing or disabled and the pending bit
(s:2/0) is already set.
S5/11 to S5/12
Reserved
NA
NA
S5/13
Input Filter
Selection Modified
Status
This bit is set whenever the discrete input filter selection in
the controller is made compatible with the hardware. Refer
to page A–6 for more information.
S5/14 to S5/15
Reserved
NA
NA
S6
Major Error Code
Status
A hexadecimal code is entered in this word by the controller
when a major error is declared. Refer to S:1/13. The code
defines the type of fault, as indicated on the following pages.
This word is not cleared by the controller.
Error codes are presented, stored, and displayed in a
hexadecimal format.
If you enter a fault code as a parameter in an instruction in
your ladder program, you must convert the code to decimal.
Application note: You can declare your own application
specific major fault by writing a unique value to S:6 and then
setting bit S:1/13.
Interrogate the value of S:6 in the user-fault routine to
determine the type of fault that occurred.
Fault Classifications: Faults are classified as Non-User,
Non-Recoverable, and Recoverable.
Error code descriptions and classifications are listed on the
following pages. Categories are:
•
power up errors
•
going-to-run errors
•
run errors
•
download errors
NA = Not Applicable