Using mounting screws, Mounting your controller vertically – Rockwell Automation 1761-HHP-B30 MicroLogix 1000 with Hand-Held Programmer (HHP) User Manual
Page 30
Chapter 1
Installing Your Controller
1–14
To remove your controller from the DIN rail:
2. Holding the controller, pry downward on
the latch until the controller is released
from the DIN rail.
1. Place a screwdriver in the DIN rail latch at
the bottom of the controller.
Side View
DIN
Rail
20147
Using Mounting Screws
To install your controller using mounting screws:
2. Secure the template to the mounting
surface. (Make sure your controller
is spaced properly.)
1. Use the mounting template from
page A–8.
5. Mount the controller.
4. Remove the mounting template.
3. Drill holes through the template.
Important: Leave the protective wrap
attached until you are
finished wiring the controller.
Mounting
Template
Protective Wrap
(remove after wiring)
Mounting Your Controller Vertically
Your controller can also be mounted vertically within an enclosure using
mounting screws or a DIN rail. To insure the stability of your controller, we
recommend using mounting screws.
To insure the controller’s reliability, the following environmental
specifications must not be exceeded.
Description:
Specification:
Operating
Temperature
0
°
C to +40
°
C (+32
°
F to +113
°
F)
➀
Operating Shock
(Panel mounted)
9.0g peak acceleration (11
±
1 ms duration)
3 times each direction, each axis
Operating Shock
(DIN rail mounted)
7.0g peak acceleration (11
±
1 ms duration)
3 times each direction, each axis
➀
DC input voltage derated linearly from +30
°
C (30V to 26.4V).
Note: When mounting your controller vertically, the nameplate should be
facing downward.
A
A
A
A
Top
Bottom
Side
Side
A. Greater than or equal
to 50.8 mm (2 in.).