Chapter 14
Using High-Speed Counter Instructions
14–11
Bidirectional Counter with Reset and Hold (Pulse/direction)
Input State
High-Speed
Count r
Input Count
(I/0)
Input
Direction (I/1)
Input Reset
(I/2)
Input Hold
(I/3)
HSC Rung
High-Speed
Counter
Action
Turning
Off-to-On
Off
Off, On, or
Turning Off
Off
True
Count Up
Turning
Off-to-On
On
Off, On, or
Turning Off
Off
True
Count Down
NA
NA
Off, On, or
Turning Off
NA
False
Hold Count
NA
NA
Off, On, or
Turning Off
On
NA
Hold Count
Off, On, or
Turning Off
NA
Off, On, or
Turning Off
NA
NA
Hold Count
NA
NA
Turning On
NA
NA
Reset to 0
NA (Not Applicable)
Bidirectional Counter (Up/down count)
Input State
High-Sp d
Input Up
Count (I/0)
Input Down
Count (I/1)
HSC Rung
High-Speed
Counter Action
Turning
Off-to-On
Off, On, or
Turning Off
True
Count Up
Off, On, or
Turning Off
Turning
Off-to-On
True
Count Down
NA
NA
False
Hold Count
NA (Not Applicable)
Bidirectional Counter with Reset and Hold (Up/down count)
Input State
High-Speed
Count r
Input Up
Count (I/0)
Input Down
Count (I/1)
Input Reset
(I/2)
Input Hold
(I/3)
HSC Rung
High-Speed
Counter
Action
Turning
Off-to-On
Off, On, or
Turning Off
Off, On, or
Turning Off
Off
True
Count Up
Off, On, or
Turning Off
Turning
Off-to-On
Off, On, or
Turning Off
Off
True
Count Down
NA
NA
Off, On, or
Turning Off
NA
False
Hold Count
NA
NA
Off, On, or
Turning Off
On
NA
Hold Count
Off, On, or
Turning Off
Off, On, or
Turning Off
Off, On, or
Turning Off
NA
NA
Hold Count
NA
NA
Turning On
NA
NA
Reset to 0
NA (Not Applicable)