Encoder freq, Pulse freq, Mop freq – Rockwell Automation 1336Z SPIDER - FRN 2.xxx-5.xxx User Manual
Page 78: Heatsink temp, Power ol count, Motor ol count, Last fault

7–6
Programming
[Encoder Freq]
Not available.
Parameter Number
63
Parameter Type
Read Only
Display Units / Drive Units
0.01 Hertz / 32767 = Maximum Freq
Factory Default
None
Minimum Value
–400.00 Hz
Maximum Value
+400.00 Hz
[Pulse Freq]
– Stand-Alone Version Only
This parameter displays the frequency command present
at the pulse input terminals. This value is displayed
whether or not this is the active frequency command.
Parameter Number
254
Parameter Type
Read Only
Display Units / Drive Units
0.01 Hertz / 32767 = Maximum Freq
Factory Default
None
Minimum Value
–400.00 Hz
Maximum Value
+400.00 Hz
[MOP Freq]
– Stand-Alone Version Only
This parameter displays the frequency command from the
MOP. The MOP frequency command can be adjusted by
TB5 & TB6 (if present) and appropriate inputs are selected
(see page
). Some SCANport adapters,
including the RIO Adapter, can also adjust the MOP
frequency command. This value is displayed whether or
not this is the active frequency command.
Parameter Number
137
Parameter Type
Read Only
Display Units / Drive Units
0.01 Hertz / 32767 = Maximum Freq
Factory Default
None
Minimum Value
0.00 Hz
Maximum Value
400.00 Hz
[Heatsink Temp]
This parameter displays the heatsink temperature of the
drive.
Parameter Number
70
Parameter Type
Read Only
Display Units / Drive Units
1
°
C / Deg. C
Factory Default
None
Minimum Value
0
Maximum Value
255
°
C
[Power OL Count]
Displays the percentage of accumulated I
2
t for the drive
thermal overload protection. Running continuously above
131% of drive rated amps will accumulate a value of 100% and
generate a Power Overload Fault (F64).
Parameter Number
84
Parameter Type
Read Only
Display Units / Drive Units
1 % / 4096 = 100%
Factory Default
None
Minimum Value
0%
Maximum Value
200%
[Motor OL Count]
This parameter displays the percentage of accumulated
I
2
t for the motor overload protection. Running continuously at
programmed [Overload Amps] will accumulate approximately
70%. Reduction of load will reduce the OL count. 100% value
will generate an Overload Fault (F07).
Parameter Number
202
Parameter Type
Read Only
Display Units / Drive Units
1 % / 4096 = 100%
Factory Default
None
Minimum Value
0%
Maximum Value
200%
[Last Fault]
This parameter displays the last drive fault. It is updated
whenever a new fault occurs.
Parameter Number
4
Parameter Type
Read Only
Display Units / Drive Units
Fault Number / Fault Number
Factory Default
None
Minimum Value
None
Maximum Value
None
Frequency
Displayed
Incoming Pulse Rate (Hz)
[Pulse Scale]
=