Output devices, Output devices –12, Drive output disconnection – Rockwell Automation 1336Z SPIDER - FRN 2.xxx-5.xxx User Manual
Page 22

2–12
General Installation for All Drives
How to Measure Motor Cable Lengths Limited by Capacitance
Table 2.E
Maximum Motor Cable Length Restrictions in meters (feet) - 380V-480V Drives
1
This current is only possible with synchronous motors and for spinning applications. For actual motor current rating, refer to Appendix A.
Output Devices
Drive Output Disconnection
180 (590)
15 (50)
15 (50)
15 (50)
90 (295)
90 (295)
165 (540)
All examples represent motor cable length of 180 meters (590 feet).
150 (490)
PWR
RUN
STOP
FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
DEVICE IS LIVE UP TO
180SEC AFTER REMOVING
MAINS VOLTAGE.
GERÄT FÜHRT BIS
180SEK NACH DEM
AUSSCHALTEN SPANNUNG.
L'APPAREIL RESTE SOUS
TENSION JUSQU'A 180 S
APRES LA MISE HORS SERVICE.
PE
PWR
RUN
STOP
FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
DEVICE IS LIVE UP TO
180SEC AFTER REMOVING
MAINS VOLTAGE.
GERÄT FÜHRT BIS
180SEK NACH DEM
AUSSCHALTEN SPANNUNG.
L'APPAREIL RESTE SOUS
TENSION JUSQU'A 180 S
APRES LA MISE HORS SERVICE.
PE
PWR
RUN
STOP
FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
DEVICE IS LIVE UP TO
180SEC AFTER REMOVING
MAINS VOLTAGE.
GERÄT FÜHRT BIS
180SEK NACH DEM
AUSSCHALTEN SPANNUNG.
L'APPAREIL RESTE SOUS
TENSION JUSQU'A 180 S
APRES LA MISE HORS SERVICE.
PE
PWR
RUN
STOP
FAULT
TB1
TB2
TB3
TB4
TB5
TB6
TB7
DEVICE IS LIVE UP TO
180SEC AFTER REMOVING
MAINS VOLTAGE.
GERÄT FÜHRT BIS
180SEK NACH DEM
AUSSCHALTEN SPANNUNG.
L'APPAREIL RESTE SOUS
TENSION JUSQU'A 180 S
APRES LA MISE HORS SERVICE.
PE
Drive Catalog
Number
Peak
Current
Rating
1
Cable
Diameter
mm
2
(AWG)
No External Devices
1321-3R55-A Reactor at Drive
1321-3R25-A Reactor at Drive
Motor Insulation Class
not less than . . .
Motor Insulation Class
not less than . . .
Motor Insulation Class
not less than . . .
220-240V AC
800V
1000V
1200V
800V
1000V
1200V
1336Z- _ A022
21.6A
2.5 (12)
120 (394)
120 (394)
120 (394)
180 (590)
180 (590)
180 (590)
1336Z- _ A036
36.0A
2.5 (12)
180 (590)
180 (590)
180 (590)
180 (590)
180 (590)
180 (590)
1336Z- _ A060
60.0A
6.0 (8)
180 (590)
180 (590)
180 (590)
180 (590)
180 (590)
180 (590)
380-400V AC
1000V
1200V
1400V
1000V
1200V
1400V
1000V
1200V
1400V
1336Z- _ B010
9.9A
2.5 (12)
15 (50)
105 (344)
105 (344)
30 (98)
180 (590)
180 (590)
60 (197)
1336Z- _ B017
16.5A
2.5 (12)
15 (50)
115 (377)
115 (377)
30 (98)
180 (590)
180 (590)
60 (197)
1336Z- _ B033
33.0A
6.0 (8)
15 (50)
155 (509)
180 (590)
30 (98)
180 (590)
180 (590)
60 (197)
460-480V AC
1200V
1400V
1600V
1200V
1400V
1600V
1200V
1400V
1600V
1336Z- _ B010
9.9A
2.5 (12)
15 (50)
105 (344)
105 (344)
30 (98)
180 (590)
180 (590)
60 (197)
1336Z- _ B017
16.5A
2.5 (12)
15 (50)
115 (377)
115 (377)
30 (98)
180 (590)
180 (590)
60 (197)
1336Z- _ B033
33.0A
6.0 (8)
15 (50)
120 (394)
180 (590)
30 (98)
180 (590)
180 (590)
60 (197)
!
ATTENTION: To guard against drive damage, always dis-
able the drive before disconnecting the motor from the drive
output terminals. Any disconnecting means wired to the
drive output terminals U, V and W must be capable of dis-
abling the drive if opened during drive operation. If opened
(motor disconnected) during drive operation, the drive will
continue to produce output voltage between U, V, & W
(drive damage could occur). An auxiliary contact must be
used to simultaneously disable the drive.