Blwn fuse flt, Low bus fault, Fault data – Rockwell Automation 1336Z SPIDER - FRN 2.xxx-5.xxx User Manual
Page 105: Flt motor mode, Flt power mode
Programming
7–33
[Blwn Fuse Flt]
– Not Available with SPIDER Drive
Enabling this parameter will allow monitoring of the bus
fuse (in 30 kW/40 HP and up drives) and cause a “Blwn
Fuse Flt” (F58).
Parameter Number
81
Parameter Type
Read and Write
Factory Default
“Enabled”
Units
Display Drive
“Disabled” 0
No Fault Generated
“Enabled” 1
Blwn Fuse Flt Generated
[Low Bus Fault]
This parameter enables or disables the drive fault condition
for bus voltage below the Bus Undervoltage Trip value set
by [Min Bus Volts].
Parameter Number
91
Parameter Type
Read and Write
Factory Default
“Enabled”
Units
Display Drive
“Disabled” 0
No Fault Generated
“Enabled” 1
Undervolt Fault Generated
[Fault Data]
This parameter displays fault related parameter numbers
or bit array information. Certain faults generate additional
information to aid fault diagnosis. See Chapter 8 for further
information.
Parameter Number
207
Parameter Type
Read and Write
Display Units / Drive Units
Parameter # / Parameter #
Factory Default
None
Minimum Value
1
Maximum Value
255
[Flt Motor Mode]
This parameter displays the motor mode active at the time
of the last fault.
Parameter Number
143
Parameter Type
Read Only
Factory Default
None
Units
Display Drive
“1” 1
Power up sequence in progress
“2” 2
Motor connected, drive off
“3” 3
DC boost being applied
“4” 4
Motor running at [Dwell Frequency]
“5” 5
Motor accelerating
“6” 6
Motor at command speed
“7” 7
Motor decelerating
“8” 8
Motor coasting
“9” 9
Motor under DC braking
“10” 10 Waiting for fault reset - returns to 0
“11” 11 Start mode
“12” 12 Flying start search enable
“13” 13 Flying start w/encoder in process
[Flt Power Mode]
This parameter displays the power mode active at the time
of the last fault. These values can be helpful in
troubleshooting for a condition causing a fault.
Parameter Number
144
Parameter Type
Read Only
Factory Default
None
Units
Display Drive
“1” 1
Power up sequence in progress
“2” 2
Precharge in progress
“3” 3
Bus voltage being stored in memory
“4” 4
Ready for run cmnd. after power up
“5” 5
Power stage diagnostics running
“6” 6
Line loss detection occurred
“7” 7
Ready for run command after stop
“8” 8
Drive running
“9” 9
Motor flux decay delay
“10” 10 DC braking in progress
“11” 11 Drive fault occurred
“12” 12 Flying start search enabled
“13” 13 Deceleration in progress
“14” 14 SCR wake mode
“15” 15 SCR check mode
“16” 16 SCR wait mode