Anlg out 0 sel, Anlg out 1 sel, Anlg out 0 offst] [anlg out 1 offst – Rockwell Automation 1336Z SPIDER - FRN 2.xxx-5.xxx User Manual
Page 103: Anlg out 0 abs] [anlg out 1 abs, Anlg out 0 lo] [anlg out 1 lo, Anlg out 0 hi] [anlg out 1 hi, Slot b option, Slot a option

Programming
7–31
[Anlg Out 0 Sel]
– Stand-Alone Version Only
[Anlg Out 1 Sel]
– Stand-Alone Version Only
This parameter selects the source value that will drive the
analog output. This output is intended for metering only
and should not be used as process control feedback.
Parameter Number
25, 274
Parameter Type
Read and Write
Factory Default
“Frequency” Out 0
“Current” Out 1
Units
Display Drive Range
“Frequency” 0
Zerotoprogrammed[MaximumFreq]
“Current” 1
Zero to 200%
“Torque” 2
Zero to 200%
“Power” 3
Zero to 200%
“Voltage” 4
Zero to 200%
“% Motor OL” 5
Zero to 200%
“% Drive OL” 6
Zero to 200%
“Encoder” 7
See [Encoder Freq]
“Speed Error” 8
See [Speed Error]
“PI Reference” 9
See [PI Reference]
“PI Feedback” 10
See [PI Feedback]
“PI Error” 11
See [PI Error]
“PI Output” 12
See [PI Output]
[Anlg Out 0 Offst]
[Anlg Out 1 Offst]
This parameter enables the voltage or current offset for the
analog output. This internal value offsets 0-20mA to 4-
20mA and 0-10V to 2-10V.
Parameter Number
154, 278
Parameter Type
Read and Write
Factory Default
“Disabled”
Units
Display Drive
“Disabled” 0
“Enabled” 1
[Anlg Out 0 Abs]
[Anlg Out 1 Abs]
This parameter selects whether a signed value or absolute
value is used for analog out.
Parameter Number
233, 277
Parameter Type
Read and Write
Factory Default
“Enabled”
Units
Display Drive
“Disabled” 0
“Enabled” 1
[Anlg Out 0 Lo]
[Anlg Out 1 Lo]
Sets the percentage of voltage or current output that rep-
resents the low end of the “Range” listed in [Anlg Out Sel].
Parameter Number
234, 275
Parameter Type
Read and Write
Display Units / Drive Units
0.1% / 4096 = 100%
Factory Default
0.0%
Minimum Value
–300.0%
Maximum Value
+300.0%
[Anlg Out 0 Hi]
[Anlg Out 1 Hi]
Sets the percentage of voltage or current output that rep-
resents the high end of the “Range” listed in [Anlg Out Sel].
Example: To get 150% of current to equal 10V/20mA, set
this parameter to 150%.
Parameter Number
235, 276
Parameter Type
Read and Write
Display Units / Drive Units
0.1% / 4096 = 100%
Factory Default
100.0%
Minimum Value
–300.0%
Maximum Value
+300.0%
[Slot B Option]
– Stand-Alone Version Only
[Slot A Option]
– Stand-Alone Version Only
Displays the catalog number of the analog I/O option board
currently installed in slots A and/or B.
Parameter Number
252, 253
Parameter Type
Read Only
Factory Default
“Standard”
Units
Display Drive
“Standard” 0
“LA1” 1
“LA2” 2
“LA3” 3
“LA4” 4
“LA5” 5
“LA6” 6
“LA7” 7
“Undefined” 8
Board not recognized