Speed ki, Speed kp, Speed error – Rockwell Automation 1336Z SPIDER - FRN 2.xxx-5.xxx User Manual
Page 122: Speed integral, Speed adder, Slip adder, Motor np rpm, Motor np hertz
7–50
Programming
[Speed KI]
This parameter contains the integral gain value for the
velocity loop during closed loop operation.
Parameter Number
165
Parameter Type
Read and Write
Display Units / Drive Units
Numeric / Gain x 100
Factory Default
100
Minimum Value
0
Maximum Value
20000
[Speed KP]
Not functional at time of printing – will set the proportional
gain for the speed loop.
Parameter Number
164
Parameter Type
Read and Write
Display Units / Drive Units
Numeric / Gain x 100
Factory Default
0
Minimum Value
0
Maximum Value
20000
[Speed Error]
This parameter displays the difference between [Freq
Command] and feedback speed.
Parameter Number
166
Parameter Type
Read Only
Display Units / Drive Units
0.01 Hertz / 32767 = Maximum Freq.
Factory Default
None
Minimum Value
– 8.33% of [Base Frequency]
Maximum Value
+8.33% of [Base Frequency]
[Speed Integral]
This parameter displays the integral value from the speed
loop.
Parameter Number
167
Parameter Type
Read Only
Display Units / Drive Units
0.01 Hertz / 32767 = Maximum Freq.
Factory Default
None
Minimum Value
–8.33% of [Base Frequency]
Maximum Value
+8.33% of [Base Frequency]
[Speed Adder]
This parameter displays the amount of correction applied
to the [Freq Command].
Parameter Number
168
Parameter Type
Read Only
Display Units / Drive Units
0.01 Hertz / 32767 = Maximum Freq.
Factory Default
None
Minimum Value
– 8.33% of [Base Frequency]
Maximum Value
+8.33% of [Base Frequency]
[Slip Adder]
This parameter displays the amount of correction added
by slip comp or phase lock loop.
Parameter Number
255
Parameter Type
Read Only
Display Units / Drive Units
0.01 Hertz / 32767 = Maximum Freq.
Factory Default
None
Minimum Value
–8.33% of [Base Frequency]
Maximum Value
+8.33% of [Base Frequency]
[Motor NP RPM]
This value should be set to the motor nameplate rated
RPM.
This parameter cannot be changed while the drive is
running.
Parameter Number
177
Parameter Type
Read and Write
Display Units / Drive Units
1 RPM / RPM x 10
Factory Default
1750 RPM
Minimum Value
60 RPM
Maximum Value
24000 RPM
[Motor NP Hertz]
This value should be set to the motor nameplate rated
frequency.
This parameter cannot be changed while the drive is
running.
Parameter Number
178
Parameter Type
Read and Write
Display Units / Drive Units
1 Hertz / Hertz x 10
Factory Default
60 Hz
Minimum Value
1 Hz
Maximum Value
400 Hz