Rockwell Automation 1336Z SPIDER - FRN 2.xxx-5.xxx User Manual
Page 31
Installation/Wiring for Stand-Alone Drives
3–7
Example 1
3 Wire Control - Application calls for a local Human Interface
Module (HIM) speed command or remote 4-20mA from a PLC. The
drive is programmed as follows:
•
[Freq Select 1] = Adapter 1
•
[Freq Select 2] = Analog Input 0
With Speed Select inputs 2 & 3 open and the selector switch set to
“Remote” (Speed Select 1 closed), the drive will follow [Freq Select
2] (Analog Input 0). With the switch set to “Local” (Speed Select 1
open) all speed select inputs are open and the drive will follow the
local HIM (Adapter 1) as selected with [Freq Select 1].
Example 2
Application is to follow a local HIM unless a preset speed is selected.
The drive is programmed as follows:
•
[Freq Select 1] = Adapter 1
•
[Freq Select 2] = Preset Freq 1
•
[Preset Freq 1] = 10 Hz.
•
[Preset Freq 2] = 20 Hz.
•
[Preset Freq 3] = 30 Hz.
Contact operation for the speed select switch is described in the table
below. If the user does not select an input as Speed Select 3, [Preset
Freq 4-7] would not be available.
Switch
Position
Speed Select Input
Parameter Used for
Speed Ref.
Programmed
Setting
1 (#28)
2 (#27)
Local
Open
Open
[Freq Select 1]
Adapter 1
1
Closed
Open
[Freq Select 2]
Preset Freq 1
2
Open
Closed
[Preset Freq 2]
20 Hz.
3
Closed
Closed
[Preset Freq 3]
30 Hz.
Speed Select 1
Speed Select 2 (Open)
Speed Select 3 (Open)
26
Local
Remote
27
28
26
Speed Select 2
Speed Select 1
Local
See Table
1 2
3
27
28