beautypg.com

Rockwell Automation 1336Z SPIDER - FRN 2.xxx-5.xxx User Manual

Page 50

background image

5–6

Human Interface Module

Control Status (except Series A HIMs below version 3.0)
Permits the drive logic mask to be disabled/enabled allowing HIM
removal while drive power is applied. Disabling the logic mask with a
Series A HIM below version 3.0 can be accomplished with [Logic
Mask] as explained on page 5–13. This menu also provides access to
a fault queue which will list the last four faults that have occurred.
“Trip” displayed with a fault indicates the actual fault that tripped the
drive. A clear function clears the queue - it will not clear an active
fault.

Password
The Password mode protects the drive parameters against programming
changes by unauthorized personnel. When a password has been
assigned, access to the Program/EEProm modes and the Control Logic/
Clear Fault Queue menus can only be gained when the correct
password has been entered. The password can be any five digit number
between 00000 and 65535. Refer to the example on page 5–13.

Figure 5.4
HIM Programming Steps

Choose Mode

Display

Choose Mode

Program

Choose Mode

Start Up

1

Choose Mode

Password

Choose Mode

EEPROM

Choose Mode

Search

1

Choose Mode

Control Status

1

Login, Logout

Modify

Parameter Groups

(See Chapter 7)

Parameters

(See Chapter 7)

Choose Mode

Process

Process Display

Save Values

3

Recall Values

3

Reset Defaults

HIM -> Drive

2

Drive -> HIM

2

OPERATOR LEVEL

MODE LEVEL

GROUP LEVEL

PARAMETER LEVEL

Control Logic,

Fault Queue

1

Not available on Series A HIMs (below version 3.0).

Power-Up Mode &

Status Display

ESC

SEL

or

or

or

or

(Read Only)

(Read Only)

(Read/Write)

2

Not available on all HIMs – Refer to Table 3.A.

3

Reserved for future use.