Rockwell Automation 1336Z SPIDER - FRN 2.xxx-5.xxx User Manual
Page 27

Installation/Wiring for Stand-Alone Drives
3–3
Figure 3.2
Digital I/O Default Settings
19
20
21
TB5
TB4
TB6
TB7
22
23
24
25
26
27
28
29
30
1
See
Speed Select Table.
2
If this mode is selected, the status of all inputs can be read at the [Input Status] parameter.
However, only “Stop/Fault Reset” and “Enable” will have control function.
3
These inputs must be present (reprogram if necessary) before drive will start.
4
Bit 0 of [Direction Mask] must = 1 to allow TB5 direction change/bipolar operation.
Input Mode (Start/Stop Functions Only)
Status
2
(Factory Default)
2-Wire Control
Single-Source Control
3-Wire Control
Single-Source Reversing
Common
Rev/For
4
(Programmable)
Factory
Default Inputs
Jog (Programmable)
Auxiliary
3
(Programmable)
Common
Speed Select 3
1
(Programmable)
Speed Select 2
1
(Programmable)
Speed Select 1
1
(Programmable)
Common
Enable
3
(Not Programmable)
Status Only
Default Mode
shown at right
is not active
when
[Input Mode]
is set to "Status"
Input 1
Input 2
Common
Input 3
Input 4
Input 5
Common
Input 6
Input 7
Input 8
Common
Input 9
24V Common
24V
Stop/Fault Reset
3
Enable
3
Stop/Fault Reset
3
Stop/Fault Reset
3
Status
Run Forward
Start
!
ATTENTION: A hazard of personal injury from
automatic restart exists with 2-wire control. 2-wire
control uses maintained Run contacts that act as both
Run (closed) and Stop (open) devices. Opening the Stop
contact (terminal 20) will stop the drive. If this contact
is reclosed, any fault will be reset. If a valid Start
command is still present, the drive will restart. Only use
2-wire control for applications outlined in NFPA79,
“Under Voltage Protection.”
If a 3-wire device (i.e. HIM) is also used, pressing the
HIM Stop key will also stop the drive. Releasing the
Stop key will clear any faults that are present, but the
drive will not restart without cycling the Start contact.