Rockwell Automation 1336Z SPIDER - FRN 2.xxx-5.xxx User Manual
Page 64

6–6
Start-Up
Program Input Mode
Cycle Input Power
4. It is important that the Input Mode selected be programmed into the drive.
Since the control inputs are programmable, incorrect operation can occur if an
improper mode is selected. The factory default mode (”Status”) disables all
inputs except Stop and Enable. Verify your control scheme against the infor-
mation provided in Chapter 3 or 4 and program the [Input Mode] parameter as
follows:
A. From the Status Display, press the Enter key (or any key). “Choose Mode”
will be displayed.
B. Press the Increment (or Decrement) key until “Program” is displayed. If
Program is not available, programming is password protected. Refer to
Chapter 5 for Password mode information.
C. Press Enter.
D. Press the Increment key until “Setup” is displayed.
E. Press Enter.
F.
Press SELect. The first character of line 2 will now flash.
G. Press the Increment or Decrement keys until the desired mode is displayed,
then press Enter.
In addition to the mode, Inputs 3-8 can also be programmed (if defaults
are not desired). See Chapter 7 for parameter information. Use the steps
above as a guide if input programming is desired.
H. Press the ESCape key (3 times) to return to the Status Display.
I.
Remove power to the drive. When the HIM Display is no longer illuminated,
reapply power.
Important: Display must go blank for input mode programming changes
to take effect.
Choose Mode
EEProm
Choose Mode
Program
Metering
Setup
Input Mode
Status
Input Mode
3 Wire
Stopped
+0.00 Hz
Advanced Start-Up Procedure
Press these keys . . .
while following these steps . . .
The HIM Display will show . . .
or
or