Specifications and Supplemental Information

A–7

Communications Data
Information Format

Drive Status Structure

This provides the drive status informa-
tion that will be sent to the logic
controllers input image table when the
Communication Module is set to con-
trol the drive.

Bit 15

Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Reference

15 14 13

12

Freq Select 1

0

0

0

0

Preset Freq 1

0

0

0

1

Preset Freq 2

0

0

1

0

Preset Freq 3

0

0

1

1

Preset Freq 4

0

1

0

0

Preset Freq 5

0

1

0

1

Preset Freq 6

0

1

1

0

Preset Freq 7

0

1

1

1

Freq Select 2

1

0

0

0

Adapter 1

1

0

0

1

Adapter 2

1

0

1

0

Adapter 3

1

0

1

1

Adapter 4

1

1

0

0

Adapter 5

1

1

0

1

Adapter 6

1

1

1

0

Jog Frequency

1

1

1

1

Local

11

10

9

TB4-6

0

0

0

1

0

0

1

2

0

1

0

3

0

1

1

4

1

0

0

5

1

0

1

6

1

1

0

Unused

1

1

1

Bit 14

Running

1 = Running
0 = Not Running

Enabled

1 = Enabled
0 = Not Enabled

Command Direction

1 = Forward
0 = Reverse

Accelerating

1 = Accelerating
0 = Not Accelerating

Rotating Direction

1 = Forward
0 = Reverse

Decelerating

1 = Decelerating
0 = Not Decelerating

Alarm

1 = Alarm
0 = No Alarm

At Speed

1 = At Speed
0 = Not at Speed

Fault

1 = Faulted
0 = Not Faulted

Reference

ID

Local Adapter

ID

Logic Control Structure

This information provides the control
logic information that is sent to the
drive through the logic controllers out-
put image table when the
Communication Module is set to con-
trol the drive.

Bit 15

Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Bit 14

Direction

5

4

No Command

0

0

Forward

0

1

Reverse

1

0

Hold Direction

1

1

Time

9/11 8/10

No Command

0

0

Time 1

0

1

Time 2

1

0

Hold Time

1

1

Reference

14 13 12

No Command 0

0

0

Freq Select 1

0

0

1

Freq Select 2

0

1

0

Preset Freq 3 0

1

1

Preset Freq 4 1

0

0

Preset Freq 5 1

0

1

Preset Freq 6 1

1

0

Preset Freq 7 1

1

1

Start

1 = Start
0 = Not Start

Stop

1 = Stop
0 = Not Stop

Jog

1 = Jog
0 = Not Jog

Clear Faults

1 = Clear Faults
0 = Not Clear Faults

Local

1 = Local Lockout
0 = Not Local

MOP Increment

1 = Increment
0 = Not Increment

MOP Decrement

1 = Decrement
0 = Not Decrement

Reference Select

Decel Time

Accel Time