Dpi alarm object, Class code 0x0098 – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 301
Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
301
CIP Information Appendix B
➊ The Fault text for this error is not return by the device, and is only reported as “Fault 45”.
DPI Alarm Object
CLASS CODE 0x0098
The following class attributes will be supported:
24
Power Loss
Drive DC Bus Voltage remained below 85% of nominal bus voltage.
25
Under Voltage
DC Bus Voltage fell below the minimum value.
26
Over Voltage
DC Bus Voltage exceeded the maximum value.
27
MCB EEPROM
This is a major fault which renders the ArmorStart inoperable.
28
Base EEPROM
This is a major fault which renders the ArmorStart inoperable.
29
Drive EEPROM
The drive EEPROM checksum checks have failed.
30
Wrong Base
The ArmorStart controller is connected to the wrong base type.
31
Fan RMP
The internal cooling fan is not running properly.
32
Power Unit
A major failure has been detected in the drive power section.
33
Drive I/O Brd
A failure has been detected in the drive control and I/O section.
34
Restart Retries
Automatic fault reset and run retries exceeded.
35
Drive Aux In Flt
The drive auxiliary input interlock is open inside the ArmorStart.
36
Analog Input
(PF Fault Code 29)
37
Drv Param Reset
Internal Drive Parameters (Parameters > 100) have been defaulted.
38
SCV Autotune
The drive automatic tuning function was either aborted or failed.
39
Source Brake
The source brake fuse has blown. Remove power and replace fuse.
40
Unknown Fault
—
41
DB1 Comm
Communication with an internal DB1 board has been lost.
42
DB1 Fault
A fault has been detected with the operation of the Dynamic Brake.
43
DB Switch Short
The Dynamic Brake switch is shorted.
44
Fault 44
—
45
➊
Incompatible COMM
Device
The Software revision of the Drive is not compatible with the ArmorStart.
Table 50 Bulletin 284E
Fault Code
Fault Text
Help Text
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Class Revision
UINT
1
2
Get
Number of Instances
UINT
1
3
Set
Alarm Cmd Write
USINT
0=NOP, 1=Clear Fault, 2=Clear Flt Queue
74
Get
Alarm Instance Read
UINT
The instance of the Fault Queue Entry containing information
about the Fault that tripped the Device.
6
Get
Number of Recorded Faults
UINT
The number of Faults recorded in the Fault Queue.