Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 173
![background image](/manuals/578181/173/background.png)
Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
173
Bulletin 280E/281E/284E Programmable Parameters Chapter 7
Figure 70 - Start Boost
Brake Voltage
Sets the frequency where brake
voltage is applied when Parameter
184 (Boost Select) = 0 (Custom
V/Hz) and Parameter 225 (Torque Perf
Mode) = 0 (V/Hz).
Parameter Number
186
Related Parameters
131, 132, 134, 135, 184, 185, 187,
188, 225
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
1.1%
Minimum Value
0.0%
Maximum Value
100.0%
Default Value
25.0%
Brake Frequency
Sets the frequency where brake
frequency is applied when Parameter
184 (Boost Select) = 0 (Custom V/Hz)
and Parameter 225 (Torque Perf
Mode) = 0 (V/Hz).
Parameter Number
187
Related Parameters
131, 132, 134, 135, 184, 185, 186,
188, 225
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
0.1 Hz
Minimum Value
0.0 Hz
Maximum Value
400.0 Hz
Default Value
15.0 Hz
Parameter 131 (Motor NP Volts)
Parameter 188 (Maximum Voltage)
Parameter 134 (Minimum Freq)
Parameter 187 (Break Frequency)
Parameter 132 (Motor NP Hertz)
Parameter 135 (Maximum Freq)
Frequency
Voltage
Par
amet
er 1
86 (Br
eak
Voltage)
Par
amet
er 1
86
(Star
t B
oost)