Starter setup group (bulletin 280e/281e only) – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 132
132
Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Starter Setup Group (Bulletin 280E/281E only)
FLA Setting
The motor’s full load current rating is
programmed in this parameter.
Parameter Number
106
Access Rule
GET/SET
Data Type
INT
Group
Starter Setup
Units
xx.x Amps
Minimum Value
See Table 19.
Maximum Value
See Table 19.
Default Value
See Table 19.
Table 19 - FLA Setting Ranges and Default Values (with indicated setting precision)
FLA Current Range (A)
Default Value
Minimum Value
Maximum Value
0.24
1.2
0.24
0.5
2.5
0.5
1.1
5.5
1.1
3.2
16.0
3.2
Overload Class
This parameter allows the installer to
select the overload class.
1 = Overload Class 10
2 = Overload Class 15
3 = Overload Class 20
Parameter Number
107
Access Rule
GET/SET
Data Type
USINT
Group
Starter Setup
Units
xx.x Amps
Minimum Value
1
Maximum Value
3
Default Value
1
OL Reset Level
This parameter allows the installer
select the % Thermal Capacity which
an overload can be cleared.
Parameter Number
108
Access Rule
GET/SET
Data Type
USINT
Group
Starter Setup
Units
% FLA
Minimum Value
0
Maximum Value
100
Default Value
75