Overload object, Class code 0x002c – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 295
Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
295
CIP Information Appendix B
➊ Reversing Starters and Inverter Starters only.
➋
Inverter Starters only
The following common services are implemented for the Control Supervisor
Object.
Overload Object
CLASS CODE 0x002C
No class attributes will be supported for the Overload Object.
A single instance (Instance 1) of the Overload Object is supported for DOL and
Reversing Starters. Instance 1 contains the following instance attributes.
154
Get
Starter Enclosure
WORD
Bit 0 = IP67
Bit 1 = NEMA 4x
Bits 2…15 Reserved
155
Get
Starter Options
WORD
Bit 0 = Full Keypad
Bit 1 = Safety Monitor
Bit 2 = Source Brake
Bit 3 = CP Brake
Bit 4 = Dynamic Brake
Bit 5 = Output Contactor
Bit 6 = EMI Filter
Bit 7 = 0…10V Analog In
Bits 8…15 = Reserved
156
Get
Last Pr Trip
UINT
—
157
➋
Get
DB Status
WORD
Bit 0 = DB Faulted
Bit 1 = DB Overtemp Warning
Bit 2 = DB On
Bit 3 = DB Flt Reset Inhibit
Bits 4…15 = Reserved
158
➋
Get
DB Fault
WORD
Bit 0 = DB Overtemp
Bit 1 = DB OverCurrent
Bit 2 = DB UnderCurrent
Bit 3 = DB Shorted Switch
Bit 4 = DB Open
Bit 5 = Reserved
Bit 6 = DB Bus Voltage Link Open
Bit 7 = Reserved
Bit 8 = DB Comms
Bits 9…15 = Reserved
Attribute ID
Access Rule
Name
Data Type
Value
Service Code
Implemented for:
Service Name
Class Instance
0x0E
No
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single