Bulletin 280E/281E/284E Programmable Parameters Chapter 7
Comm Override
This parameter allows for local logic to
override the absence of an I/O
connection.
0 = Disable
1 = Enable
Parameter Number
9
Access Rule
GET/SET
Data Type
BOOL
Group
Misc. Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Keypad Mode
This parameter selects if the keypad
operation is maintained or
momentary.
0 = Maintained
1 = Momentary
Parameter Number
45
Access Rule
GET/SET
Data Type
BOOL
Group
Misc. Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Keypad Disable
This parameter disables all keypad
function except for the “OFF” and
“RESET” buttons.
0 = Not Disabled
1 = Disabled
Parameter Number
46
Access Rule
GET/SET
Data Type
BOOL
Group
Misc. Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Set to Defaults
This parameter if set to “1” will set the
device to the factory defaults (but will
not cause the ArmorStart to reboot).
0 = No Operation
1 = Set to Defaults
Parameter Number
47
Access Rule
GET/SET
Data Type
BOOL
Group
Misc. Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0