Appendix B CIP Information
Instance 1 of the Identity Object will contain the following attributes:
➊ Instance 1 only
The following common services will be implemented for Instance 1. Service
requests to other instances are serviced through the bridge.
The Type 0 and 1 reset service types will reset the Control Module. The
EtherNet/IP module will perform the Type 0 or 1 reset on itself.
Attribute ID
Access Rule
Name
Data Type
Value
1 Get
Vendor
UINT
1
2 Get
Device
Type
UINT
22
3
Get
Product Code
UINT
Starter Rating specific
4 Get
Revision
Major Revision
Minor Revision
Structure of:
USINT
USINT
See table above.
5 Get
Status
WORD
Bit 0…0 = Not Owned; 1 = Owned by Master
Bit 2…0 = Factory Defaulted; 1 = Configured
Bit 8 - Minor Recoverable fault
Bit 9 - Minor Unrecoverable fault
Bit 10 - Major Recoverable fault
Bit 11 - Major Unrecoverable fault
6
Get
Serial Number
UDINT
Unique number for each device
7 Get
Product Name
String Length
ASCII String
Structure of:
USINT
STRING
Product Code specific
8
Get
State
USINT
Returns the value "3 = Operational"
9 Get
Configuration
Consistency Value
UINT "Module
FRS"
102
➊
Get Build
Number
UDINT
Build
number of EtherNet/IP Module firmware.
Service Code
Implemented for:
Service Name
Class
Instance
0x01 Yes
Yes
Get_Attributes_All
0x05 No
Yes
Reset
0x0E Yes
Yes Get_Attributes_Single