I/o assemblies, Instance 3, Instance 52 – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 282
![background image](/manuals/578181/282/background.png)
282
Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Appendix B CIP Information
I/O Assemblies
The following table summarizes the Assembly instances that are supported in the
ArmrorStart EtherNet/IP Product:
➊ These assemblies are selectable on Inverter Type ArmorStart units only.
Instances 3 and 52 are required by the ODVA Motor Starter Profile. When used
as an EtherNet/IP Class 1 connection point, the I/O data attribute is simply
passed through the bridge.
Instance 3
This is the required output (consumed) assembly.
Instance 52
This is the required input (produced) assembly.
Instance Type
Description
3
Consumed
Required ODVA Consumed Instance
52 Produced
Required
ODVA Produced Instance
150
Produced
Default Bulletin 280E/281E Produced Assembly
151
➊
Produced
Default Bulletin 284E Produced Assembly
162
Consumed
Default Consumed Instance for DOL and Reversing Starters
166
➊
Consumed
Default Consumed Instance for Inverter type Starters
191
Consumed
Empty assembly for Input Only I/O Connection
192
Consumed
Empty assembly for Listen Only I/O Connection
Instance 3 ODVA Starter
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
—
—
—
—
—
—
—
Run Fwd
Instance 52 ODVA Starter
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
—
—
—
—
—
—
Running
—
Fault