Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 198
![background image](/manuals/578181/198/background.png)
198
Rockwell Automation Publication 280E-UM001B-EN-P - July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
167
Accel Time 2
When active, sets the rate of acceleration for all speed increases
except for jog.
20.0 Secs
Drive Advanced Setup
168
Decel Time 2
When active, sets the rate of deceleration for all speed decreases
except for jog.
20.0 Secs
Drive Advanced Setup
169
Internal Freq
Provide the frequency command to drive when Parameter 138
(Speed Reference) is set to “1” (Internal Freq).
60.0 Hz
Drive Advanced Setup
170…177
Preset Freq 0
Preset Freq 1
Preset Freq 2
Preset Freq 3
Preset Freq 4
Preset Freq 5
Preset Freq 6
Preset Freq 7
Provides a fixed frequency command value when Parameters
151…154 (Digital In x Sel) is set to Option 4 (Preset
Frequencies).
See Table 22.
Drive Advanced Setup
178
Jog Frequency
Sets the output frequency when the jog command is issued.
10.0 Hz
Drive Advanced Setup
179
Jog Accel/Decel
Sets the acceleration and deceleration time when a jog command
is issued.
10.0 Secs
Drive Advanced Setup
180
DC Brake Time
Sets the length of time that DC brake current is injected into the
motor. Refer to Parameter 181 (DC Brake Level).
0.0 Secs
Drive Advanced Setup
181
DC Brake Level
Defines the maximum DC brake current, in amps, applied to the
motor when Parameter 137 (Stop Mode) is set to either Ramp or
DC Brake.
Drive Rated Amps x
0.05
Drive Advanced Setup
182
DB Resistor Sel
Used to set percent duty cycle for external dynamic braking.
0 = Disabled
Drive Advanced Setup
183
S Curve %
Sets the percentage of acceleration or deceleration time that is
applied to ramp as S Curve. Time is added, half at the beginning
and half at the end of the ramp.
0% (Disabled)
Drive Advanced Setup
184
Boost Select
Sets the boost voltage (% of Parameter 131 (Motor NP Volts))
and redefines the Volts per Hz curve. Active when Parameter 225
(Torque Perf Mode) = 0 (V/Hz). Drive may add additional voltage
unless Option 5 is selected.
8 = 5.0 (2.5 for 5 Hp
drives)
Drive Advanced Setup
185
Start Boost
Sets the boost voltage (% of Parameter 131 (Motor NP Volts))
and redefines the Volts per Hz curve when Parameter 184 (Boost
Select) = 0 (Custom V/Hz) and Parameter 225 (Torque Perf Mode)
= 0 (V/Hz).
2.5%
Drive Advanced Setup
186
Brake Voltage
Sets the frequency where brake voltage is applied when
Parameter 184 (Boost Select) = 0 (Custom V/Hz) and Parameter
225 (Torque Perf Mode) = 0 (V/Hz).
25.0%
Drive Advanced Setup
187
Brake Frequency
Sets the frequency where brake frequency is applied when
Parameter 184 (Boost Select) = 0 (Custom V/Hz) and Parameter
225 (Torque Perf Mode) = 0 (V/Hz).
15.0 Hz
Drive Advanced Setup
188
Maximum Voltage
Sets the highest voltage the drive will output.
Drive Rated Volts
Drive Advanced Setup
189
Current Limit 1
Maximum output current allowed before current limiting occurs.
Drive Rated Amps x
1.5
Drive Advanced Setup
190
Motor OL Select
Drive provides Class 10 motor overload protection. Setting 0…2
select the derating factor for I
2
t overload function.
0 = No Derate
Drive Advanced Setup
Table 29 - Parameter Descriptions
Parameter
Number
Parameter
Name
Description
Factory Default
Group