Bulletin 280E/281E/284E Programmable Parameters Chapter 7
OutA Net IdlValue
This parameter determines the state
that Output A assumes when the
network is idle and Parameter 37
(OutA Net IdlState) is set to “0”.
0 = Open
1 = Close
Parameter Number
38
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutB Pr FltState
This parameter in conjunction with
Parameter 40 (OutB Pr FltValue)
defines how Output B will respond
when a protection trip occurs.
0 = Goto PrFlt Value
1 = Ignore PrFlt
When set to “1”, Output B continues to
operate as command via the network.
When set to “0”, Output B will open or
close as determined by setting in
Parameter 40.
Parameter Number
39
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutB Pr FltValue
This parameter determines the state
the Out B assumes when a protection
trip occurs and Parameter 39 (OutB Pr
FltState) is set to “0”.
0 = Open
1 = Close
Parameter Number
40
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
OutB Net FltState
This parameter in conjunction with
Parameter 42 (OutB Net FltValue)
defines how Output B will respond
when a network fault occurs.
0 = Goto Idle Value
1 = Hold Last State
When set to “1”, Output B will hold
state prior to trip occurrence. When
set to “0”, Output B will open or close
as determined by setting in Parameter
42.
Parameter Number
41
Access Rule
GET/SET
Data Type
BOOL
Group
User I/O Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0