Ethernet/ip led status indication – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 211

Rockwell Automation Publication 280E-UM001B-EN-P - July 2012
211
Diagnostics Chapter 9
EtherNet/IP LED Status
Indication
EtherNet/IP LED status and diagnostics consists of four LEDs.
• Link Activity/Status LEDS
– Link1 Activity/Status (Port 1) – LED Color: Bicolor (Green/Yellow).
refer to Table 31
– Link2 Activity/Status (Port 2) – LED Color: Bicolor (Green/Yellow).
refer to Table 31
• “MOD” LED – Bicolor Red/Green represents the Ethernet Module
status, refer to Table 32
• “NET” LED – Bicolor Red/Green represents the Ethernet Network
status, refer to Table 34
Refer to Parameter 63 “Base Trip” for the Base Module Trip Status.
Figure 80 - EtherNet/IP LED
Table 31 - Link 1 or Link 2 Port Activity/Status
Link 1 or 2 Status LED
Description
Recommended Action
OFF
No link established
Verify network cabling, and correct, as needed.
Green
Link established at 100 Mbps
None
Flashing green
Transmit or receive activity present at 100 Mbps
None
Yellow
Link established at 10 Mbps
None
Flashing yellow
Transmit or receive activity present at 10 Mbps
None
Table 32 - Module Status Indicator
MOD Status LED
Summary
Requirement
Steady OFF
No power
If no power is supplied to the device, the module status indicator shall be steady OFF.
Steady Green
Device operational
If the device is operating correctly, the module status indicator shall be steady green.
Flashing Green
Standby
If the device has not been configured, the module status indicator shall be flashing
green.
Flashing Red
Minor fault
If the device has detected a recoverable minor fault, the module status indicator shall
be flashing red.
Note: An incorrect or inconsistent configuration would be considered a minor fault.
Steady Red
Major fault
If the device has detected a non-recoverable major fault, refer to Table 33.
Flashing Green/Red
Self-test
While the device is performing its power up testing, the module status indicator shall
be flashing green/red.