Standard features, Inputs, Outputs – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 24: Inputs outputs
![background image](/manuals/578181/24/background.png)
24
Rockwell Automation Publication 280E-UM001B-EN-P - July 2012
Chapter 1 Product Overview
Parameter Group “Start Protection,” Parameter 24 “PrFault Enable” is used to
enable and disable the above protection faults. Refer to Parameter 61
“LastPR Fault” for additional details of the last protection fault.
Standard Features
Inputs
The EtherNet/IP version includes four 24V DC inputs that are single keyed (two
inputs per connector) sourced from A3/A2 control power. The inputs use two
M12 Connectors. Each input has an LED status indication. They are
configurable as sinking or sourcing.
Outputs
The EtherNet/IP version includes two self-protected solid state outputs that are
single keyed (one per connector), sourced from A1/A2 control power. Outputs
are sourcing type with a maximum current per output point of 0.5 A DC. The
outputs use one M12 connectors per output, each having LED status indication.
Table 1 - Protection Faults
Bulletin 280E/281E Trip Status
Bulletin 284E Trip Status
PowerFlex 40 Fault Codes
Short Circuit
Short Circuit
—
Overload
Overload
(Drive Codes 7 and 64)
Phase Loss
Phase Short
(Drive Codes 38…43)
Reserved
Ground Fault
(Drive Code 13)
Reserved
Stall
(Drive Code 6)
Control Pwr Loss
Control Pwr Loss
—
Input Fault
Input Fault
—
Over Temperature
Over Temperature
—
Phase Imbalance
Over Current
(Drive Codes 12 and 63)
A3, Unswitched Power Loss
A3, Unswitched Power Loss
—
Reserved
Internal Comm
(Drive Code 81)
Reserved
DC Bus Fault
(Drive Codes 3, 4 and 5)
EEprom
EEprom
(Drive Code 100)
Hdw Flt
Hdw Flt
(Drive Codes 70 and 122)
Reserved
Restart Retries
(Drive Code 33)
Reserved
Misc. Fault
(Drive Codes 2, 8, 29, 48 and 80)