Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
.
Internal Freq
Provide the frequency command to
drive when Parameter 138 (Speed
Reference) is set to “1” (Internal Freq).
When enabled, this parameter will
change the frequency command in
real time.
Parameter Number
169
Related Parameters
138
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
0.1 Hz
Minimum Value
0.0
Maximum Value
400.0
Default Value
60.0
170 (Preset Freq 0) ➊
171 (Preset Freq 1)
172 (Preset Freq 2)
173 (Preset Freq 3)
174 (Preset Freq 4)
175 (Preset Freq 5)
176 (Preset Freq 6)
177 (Preset Freq 7)
Parameter Number
170…173, 174…177
Related Parameters
138…140, 151…154, 167, 168,
240…247, 250…257
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
0.1 Hz
Minimum Value
0.0
Maximum Value
400.0
Default Value
See Table 22
Table 22 - Parameters 170…177 Preset Freq Options
Values
Provides a fixed frequency command value
when Parameters 151…154 (Digital In x
Sel) is set to Option 4 (Preset Frequencies).
170 Default ➊
0.0 Hz
171 Default
5.0 Hz
172 Default
10.0 Hz
173 Default
20.0 Hz
174 Default
30.0 Hz
175 Default
40.0 Hz
176 Default
50.0 Hz
177 Default
60.0 Hz
Min./Max.
0.0/400.0 Hz
Display
0.1 Hz
Input State of Digital In 1 (I/
O Terminal 05 when
Parameter 151 = 4)
Input State of Digital In 2 (I/
O Terminal 06 when
Parameter 152 = 4)
Input State of Digital In 3 (I/
O Terminal 07 when
Parameter 153 = 4)
Frequency
Source
Accel/Decel
Parameter
Used ➋
0
0
0
170 (Preset Freq 0)
(Accel Time 1)/(Decel Time 1)
1
0
0
171 (Preset Freq 1)
(Accel Time 1)/(Decel Time 1)
0
1
0
172 (Preset Freq 2)
(Accel Time 2)/(Decel Time 2)
1
1
0
173 (Preset Freq 3)
(Accel Time 2)/(Decel Time 2)
0
0
1
174 (Preset Freq 4)
(Accel Time 3)/(Decel Time 3)