Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 174

174
Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Figure 71 - Overload Trip Curves
Maximum Voltage
Sets the highest voltage the drive will
output.
Parameter Number
188
Related Parameters
104, 185, 186, 187
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
1V AC
Minimum Value
20V AC
Maximum Value
Drive Rated Volts
Default Value
Drive Rated Volts
Current Limit 1
Maximum output current allowed
before current limiting occurs
Parameter Number
189
Related Parameters
133, 218
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
0.1 A
Minimum Value
0.1 A
Maximum Value
Drive rated amps X 1.8
Default Value
Drive rated amps X 1.5
Motor OL Select
Drive provides Class 10 motor
overload protection. Settings 0…2,
select the derating factor for I
2
t
overload function.
0 = No Derate
1 = Min. Derate
2 = Max. Derate
Parameter Number
190
Related Parameters
132, 133
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
1
Minimum Value
0
Maximum Value
2
Default Value
0
0
0
20
40
60
80
100
25 50 75 100 125 150 175 200
% of P132 [Motor NP Hertz]
No Derate
% of P133 Mot
or OL C
urr
en
t
0
0
20
40
60
80
100
25 50 75 100 125 150 175 200
% of P132 [Motor NP Hertz]
Min Derate
% of P133 Mot
or OL C
urr
en
t
0
0
20
40
60
80
100
25 50 75 100 125 150 175 200
% of P132 [Motor NP Hertz]
Max Derate
% of P133 Mot
or OL C
urr
en
t