Discrete input group object, Class code 0x001d, Discrete output group object – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 292: Class code 0x001e
![background image](/manuals/578181/292/background.png)
292
Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Appendix B CIP Information
Discrete Input Group Object
CLASS CODE 0x001D
No class attributes will be supported for the Discrete Input Group Object.
A single instance of the Discrete Input Group Object is supported and contains
the following instance attributes.
The following common services will be implemented for the Discrete Input
Group Object.
Discrete Output Group Object
CLASS CODE 0x001E
No class attributes will be supported for the Discrete Output Group Object.
Instance 1 exists for all ArmorStart units. Instance 2 exists for drive units only.
Instances 1 contains the following instance attributes.
Attribute ID
Access Rule
Name
Data Type
Value
3
Get
Number of Instances
USINT
4
4
Get
Binding
Array of UINT
List of DIP Instances
6
Get/Set
Off_On_Delay
UINT
—
7
Get/Set
Off_On_Delay
UINT
—
Service Code
Implemented for:
Service Name
Class Instance
0x0E
No
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
Attribute ID
Access Rule
Name
Data Type
Value
3
Get
Number of Instances
USINT
4 for DOL/Soft Starter 10 for Inverters
4
Get
Binding
Array of UINT
List of DOP Instances
6
Get/Set
Command
BOOL
0 = Idle, 1 = Run
104
Get/Set
Network Status Overrride
BOOL
0 = No Override (go to safe state)
1 = Override (run local logic)
105
Get/Set
Comm Status Overrride
BOOL
0 = No Override (go to safe state)
1 = Override (run local logic)