Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 167
Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
167
Bulletin 280E/281E/284E Programmable Parameters Chapter 7
Relay Out Level
Sets the trip point for the digital output relay if the value of Parameter
155 (Relay Out Sel) is 6, 7, 8, 10, 16, 17, 18, or 20.
Parameter Number
156
Related Parameters
155
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
0.1
Minimum Value
0.0
Maximum Value
9999
Default Value
0.0
Parameters 155 Setting
Parameter 156 Min./Max.
6
0/400 Hz
7
0/180%
8
0/815V
10
0/100%
16
0.1/9999 sec
17
1/9999 counts
18
1/180
°
20
0/1
Accel Time 2
When active, sets the rate of acceleration for all speed increases except for jog.
Parameter Number
167
Related Parameters
139, 151…154, 170…177,
240…247
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
0.1 sec
Minimum Value
0.0
Maximum Value
600.0
Default Value
20.0
Maximum Freq
Accel Time
--------------------------------------
Accel Rate
=
Parameter 135
(Maximum Freq)
Speed
Param.
139 or
167
(Accel
Time x)
0
0
Time
Param.
140 or
168
(Decel
Time x)
Ac
celer
ation
Dec
eler
ation
Decel Time 2
When active, sets the rate of deceleration for all speed decreases except for jog.
Parameter Number
168
Related Parameters
140, 151…154, 170…177,
240…247
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
0.1 sec
Minimum Value
0.0
Maximum Value
600.0
Default Value
20.0
Maximum Freq
Decel Time
--------------------------------------
Decel Rate
=
Parameter 135
(Maximum Freq)
Speed
Param.
139 or
167
(Accel
Time x)
0
0
Time
Param.
140 or
168
(Decel
Time x)
Ac
celer
ation
Dec
eler
ation