Starter protection group – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 123
![background image](/manuals/578181/123/background.png)
Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
123
Bulletin 280E/281E/284E Programmable Parameters Chapter 7
Starter Protection Group
Int03DeviceOut Cfg
This parameter is used to specify
Int03DeviceOut of produced assembly
150 or 151.
Parameter Number
16
Access Rule
GET/SET
Data Type
USINT
Group
Produced Assembly Config
Units
—
Minimum Value
0
Maximum Value
108
Default Value
6
Pr FltReset Mode
This parameter configures the
Protection Fault reset mode.
0 = Manual
1 = Automatic
Parameter Number
23
Access Rule
GET/SET
Data Type
BOOL
Group
Starter Protection
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Pr Fault Enable
This parameter enables the Protection
Fault by setting the bit
to 1.
Parameter Number
24
Access Rule
GET/SET
Data Type
WORD
Group
Starter Protection
Units
—
Minimum Value
12419
Maximum Value
13287
Default Value
12419