Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 178

178
Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
SW Current Trip
Enables/disables a software
instantaneous (within 100 ms)
current trip.
Parameter Number
198
Related Parameters
133
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
0.1 A
Minimum Value
0.0
Maximum Value
Drive rated amps x 2
Default Value
0.0 (Disabled)
Process Factor
Scales the output frequency value
displayed by Parameter 110 (Process
Display).
Output Freq x Process Factor = Process
Display
Parameter Number
199
Related Parameters
110
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
0.1
Minimum Value
0.1
Maximum Value
999.9
Default Value
30.0
Fault Clear
Stop drive before changing this
parameter.
Resets a fault and clears the fault
queue. Used primarily to clear a fault
over network communications.
0 = Ready/Idle (Default)
1 = Reset Fault
2 = Clear Buffer (Parameters
107…109 (Fault x Code))
Parameter Number
200
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
—
Minimum Value
0
Maximum Value
2
Default Value
0
Program Lock
Protects parameters against change
by unauthorized personnel.
0 = Unlocked
1 = Locked
Parameter Number
201
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0