Troubleshooting Chapter 10
Rapid Ring Fault
When a Rapid Ring Fault occurs, the following events occur:
• The active supervisor will block traffic on port 2, resulting in possible network segmentation, that is,
some nodes may become unreachable.
• The Link 2 status indicator on the active supervisor is off.
• As soon as the fault occurs, for both RSLogix 5000 programming software and RSLinx communication
software, the Status field = Rapid Fault/Restore Cycles.
Figure 88 - Rapid Fault/Restore Cycles Status
Any of the following may cause a Rapid Ring Fault:
• 5 intentional disconnections/reconnections of a node from the network within 30 s
• A duplex mismatch between two connected devices
• Electromagnetic noise on the network
• Unstable physical connections, such as intermittent connectors
Given the nature of a Rapid Ring Fault, the Last Active Node information may not be accurate when a
Rapid Ring Fault condition is present
Multiple possible solutions exist.
• For the disconnections and reconnections
issue, no solution is required.
Clear the fault when you have reconnected the
device to the network permanently.
• For the duplex mismatch issue, reconfigure the
duplex parameters to make sure they match
between the devices.
• For the electromagnetic noise issue, determine
where the noise exists and eliminate it or use a
protective shield in that location.
• For the unstable connections issue, determine
where they exist on the network and correct
them.
• Check the media counters for all devices on the
network. The device with the highest media
counter count is most likely causing the Rapid
Ring Fault.
• Remove devices from the network one by one.
When you see the Rapid Ring Fault disappear
after a device is removed, that device is
causing the fault.
• Finally, your Beacon Interval or Timeout
configuration may not be appropriate for your
network.
However, if you think you need to change
these values, we recommend that you call
Rockwell Automation technical support.
Once the fault is fixed, click Clear Fault.
Partial Fault
Condition
A partial network fault occurs when traffic is lost in only one direction on the network because a ring
member is not forwarding beacons in both directions for some reason, such as because of a component
failure.
The active ring supervisor detects a partial fault by monitoring the loss of Beacon frames on one port
and the fault location appears in the Ring Fault section of the Network tab.
When a partial fault is detected, the active ring supervisor blocks traffic on one port. At this point, the
ring is segmented due to the partial fault condition. The nodes adjacent to the faulted part of the
network are displayed in the Ring Fault group with either IP addresses or MAC ID’s for each node
displayed.
When this fault occurs the Network Status field = Partial Fault Condition.
Once the fault is corrected, it automatically clears, and the Network Status field returns to Normal.
Determine where the fault condition exists and
correct it.
Table 46 - Troubleshoot DLR or Linear Network
Issue
Description
Solution