Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 194
194
Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
26
Str Net FltState
This parameter in conjunction with Parameter 27 (Str
Net FltValue) defines how the starter will respond
when a fault occurs as determined by Parameter 27.
0 =
Goto Fault Value
Starter Protection
Common
27
Str Net FltValue
This parameter determines how the starter will be
commanded in the event of a fault.
0 = OFF
Starter Protection
Common
28
Str Net IdlState
This parameter determines response when Idle fault
occurs.
0 =
Goto Fault Value
Starter Protection
Common
29
Str Net IdlValue
This parameter determines the state that starter
assumes when the network is idle and Parameter 28
(Str Net IdlState) is set to “Goto Fault Value”.
0 = OFF
Starter Protection
Common
30
Off-to-On Delay
This parameter allows the installer to program a time
duration before being reported ON.
0
User I/O Configuration
Common
31
On-to-Off Delay
This parameter allows the installer to program a time
duration before being reported OFF.
0
User I/O Configuration
Common
32
In Sink/Source
This parameter allows the installer to program the
inputs to be sink or source.
0 = Sink
User I/O Configuration
Common
33
OutA Pr FltState
This parameter in conjunction with Parameter 34 (OutA
Pr FltValue) defines how Output A will respond when a
trip occurs.
0 =
Goto PrFlt Value
User I/O Configuration
Common
34
OutA Pr FltValue
This parameter determines the state the Output A.
0 = Open
User I/O Configuration
Common
35
OutA Net FltState
This parameter in conjunction with Parameter 36 (OutA
Net FltValue) defines how Output A will respond.
0 =
Goto Fault Value
User I/O Configuration
Common
36
OutA Net FltValue
This parameter determines the state that Output.
0 = Open
User I/O Configuration
Common
37
OutA Net IdlState
This parameter in conjunction with Parameter 38 (OutA
Net IdlValue) defines how Output A will respond when
the network is idle.
0 =
Goto Idle Value
User I/O Configuration
Common
38
OutA Net IdlValue
This parameter determines the state that Output A
assumes when the network is idle and Parameter 37
(OutA Net IdlState) is set to “0”.
0 = Open
User I/O Configuration
Common
39
OutB Pr FltState
This parameter in conjunction with Parameter 40 (OutB
Pr FltValue) defines how Output B will respond when a
protection trip occurs.
0 =
Goto PrFlt Value
User I/O Configuration
Common
40
OutB Pr FltValue
This parameter determines the state the Out B assumes
when a protection trip occurs and Parameter 39 (OutB
Pr FltState) is set to “0”.
0 = Open
User I/O Configuration
Common
41
OutB Net FltState
This parameter in conjunction with Parameter 42 (OutB
Net FltValue) defines how Output B will respond when
a network fault occurs.
0 =
Goto Idle Value
User I/O Configuration
Common
42
OutB Net FltValue
This parameter determines the state that Output B
assumes when a network fault occurs and Parameter
41 (OutB Net FltState) is set to “0”.
0 = Open
User I/O Configuration
Common
43
OutB Net IdlState
This parameter in conjunction with Parameter 44 (OutB
Net IdlValue) defines how Output B will respond when
the network is idle.
0 =
Goto PrFlt Value
User I/O Configuration
Common
Table 28 - ArmorStart Common Parameters
Parameter
Number
Parameter Name
Description
Factory Default
Group
Controller