beautypg.com

Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual

Page 179

background image

Rockwell Automation Publication 280E-UM001B-EN-P – July 2012

179

Bulletin 280E/281E/284E Programmable Parameters Chapter 7

Testpoint Sel

Used by Rockwell Automation field
service personnel.

Parameter Number

202

Related Parameters

119

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

1 Hex

Minimum Value

0

Maximum Value

FFFF

Default Value

400

Comm Data Rate

This parameter is not available for

use with the ArmorStart Distributed

Motor Controller.

Parameter Number

203

CommNode Addr

This parameter is not available for

use with the ArmorStart Distributed

Motor Controller.

Parameter Number

204

Comm Loss Action

Selects the drive’s response to a loss of
the communication connection or
excessive communication errors.
0 = Fault (Default)
Drive will fault on an F81 Comm Loss
and coast to stop
1 = Coast Stop
Stops drive via coast to stop
2 = Stop
Stops via Parameter 137 (Stop Mode)
setting
3 = Continue Last
Drive continues operating at
communication commanded speed
saved in RAM.

Parameter Number

205

Related Parameters

115, 137, 206

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

Minimum Value

0

Maximum Value

3

Default Value

0