Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 179
Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
179
Bulletin 280E/281E/284E Programmable Parameters Chapter 7
Testpoint Sel
Used by Rockwell Automation field
service personnel.
Parameter Number
202
Related Parameters
119
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
1 Hex
Minimum Value
0
Maximum Value
FFFF
Default Value
400
Comm Data Rate
This parameter is not available for
use with the ArmorStart Distributed
Motor Controller.
Parameter Number
203
CommNode Addr
This parameter is not available for
use with the ArmorStart Distributed
Motor Controller.
Parameter Number
204
Comm Loss Action
Selects the drive’s response to a loss of
the communication connection or
excessive communication errors.
0 = Fault (Default)
Drive will fault on an F81 Comm Loss
and coast to stop
1 = Coast Stop
Stops drive via coast to stop
2 = Stop
Stops via Parameter 137 (Stop Mode)
setting
3 = Continue Last
Drive continues operating at
communication commanded speed
saved in RAM.
Parameter Number
205
Related Parameters
115, 137, 206
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
—
Minimum Value
0
Maximum Value
3
Default Value
0