Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Drive Advanced Setup Group (Bulletin 284E only)
Reset To Defaults
Resets all parameter values to factory
defaults.
0 = Ready/Idle (Default)
1 = Factory Rset
Parameter Number
141
Access Rule
GET/SET
Data Type
BOOL
Group
Drive Setup
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Motor OL Ret
Enables/disables the Motor overload
Retention function. When Enabled,
the value held in the motor overload
counter is saved at power-down and
restored at power-up. A change to this
parameter setting resets the counter.
0 = Disabled (Default)
1 = Enabled
Parameter Number
143
Access Rule
GET/SET
Data Type
BOOL
Group
Drive Setup
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Digital In 1 SEL (151)
Digital In 2 SEL (152)
Digital In 3 SEL (153)
Digital In 4 SEL (154)
Selects the function for the digital
inputs.
Parameter Number
151…154
Related Parameters
112, 114, 138…140, 167, 168,
170…179, 240…247
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
See Table 20 for details.
Minimum Value
Maximum Value
Default Value
Stop drive before changing this
parameter.
O
Stop drive before changing this
parameter.
O